Emerson OpenComms-485 manual Liebert UPS Series, Data Point

Models: OpenComms-485

1 39
Download 39 pages 12.67 Kb
Page 26
Image 26

REV. 5 7/6/2007

Liebert Monitoring Group –Development

Input Current L2

30204

1

1

A

Input Voltage L3

30253

1

1

V

Input Current L3

30254

1

1

A

 

 

 

 

 

Liebert UPS Series 600

Supported Modbus Points

Data Point

Status

Coil

# of

Scale

Notes / Units

 

 

 

Reg.

 

 

Battery Charger On

10044

 

1

1

 

Battery Charge

10046

 

1

1

 

Compensation

 

 

 

 

 

Inverter Ready

10047

 

1

1

 

Auto Retransfer

10049

 

1

1

 

Primed

 

 

 

 

 

Load On Inverter

10073

 

1

1

 

Load On Bypass

10074

 

1

1

 

Buck On

10076

 

1

1

 

Battery data Buffer Full

10084

 

1

1

 

Shutdown Reason –

10096

 

1

1

 

Hardware

 

 

 

 

 

Load On Battery

10128

 

1

1

 

Manual Reset Transfer

10130

 

1

1

 

Load On Bypass

10133

 

1

1

 

Permanent

 

 

 

 

 

Load On Bypass-UPS

10134

 

1

1

 

fault

 

 

 

 

 

Battery Switch Open

10136

 

1

1

 

Input Switch Open

10137

 

1

1

 

Output Switch open

10138

 

1

1

 

Emergency Load

10145

 

1

1

 

Transfer to Inverter

 

 

 

 

 

Transfer inhibited –

10146

 

1

1

 

Asynchronous

 

 

 

 

 

Sources

 

 

 

 

 

Transfer inhibited –

10147

 

1

1

 

over predefined limit

 

 

 

 

 

SBS SCR Open

10149

 

1

1

 

SBS SCR Short

10150

 

1

1

 

Low Battery -

10152

 

1

1

 

Shutdown Imminent

 

 

 

 

 

Output Overload

10154

 

1

1

 

Over Temperature

10171

 

1

1

 

Warning

 

 

 

 

 

Battery Over

10172

 

1

1

 

Temperature CB Trip

 

 

 

 

 

Input Power Supply

10186

 

1

1

 

Fail

 

 

 

 

 

Input Under Voltage

10188

 

1

1

 

Input Brown Out

10189

 

1

1

 

 

 

 

 

 

 

23

Page 26
Image 26
Emerson OpenComms-485 manual Liebert UPS Series, Data Point