REV. 5 7/6/2007

Liebert Monitoring Group –Development

 

Humidification On

10030

-

1

 

 

 

HumSym

 

Dehumidification On

 

 

10031

 

-

 

1

 

 

 

DehumSym

 

 

 

 

 

 

 

 

 

HornSym

 

Audible Alarm On

10032

-

1

 

 

 

 

Reserved

 

 

10033

 

-

 

1

 

 

 

087

 

 

MAIN FAN OVERLOAD

10034

-

1

 

006

 

 

LOSS OF AIRFLOW

 

 

10035

 

-

 

1

 

 

 

007

 

 

LOSS OF FLOW

10036

-

1

 

107

 

 

COMP 1 HIGH PRESSURE

 

 

10037

 

-

 

1

 

 

 

001

 

 

COMP 1 LOW PRESSURE

10038

-

1

 

002

 

 

COMP 1 OVERLOAD

 

 

10039

 

-

 

1

 

 

 

071

 

 

COMP 1 PUMPDOWN FAIL

10040

-

1

 

091

 

 

COMP 2 HIGH PRESSURE

 

 

10041

 

-

 

1

 

 

 

058

 

 

COMP 2 LOW PRESSURE

10042

-

1

 

059

 

 

COMP 2 OVERLOAD

 

 

10043

 

-

 

1

 

 

 

072

 

 

COMP 2 PUMPDOWN FAIL

10044

-

1

 

096

 

 

DIG SCROLL1 HIGH TEMP

 

 

10045

 

-

 

1

 

 

 

097

 

 

DIG SCROLL2 HIGH TEMP

10046

-

1

 

098

 

 

SMOKE DETECTED

 

 

10047

 

-

 

1

 

 

 

104

 

 

WATER UNDER FLOOR

10048

-

1

 

105

 

 

HUMIDIFIER PROBLEM

 

 

10049

 

-

 

1

 

 

 

086

 

 

STBY GLYCOL PUMP ON

10050

-

1

 

108

 

 

STANDBY UNIT ON

 

 

10051

 

-

 

1

 

 

 

109

 

 

COND PUMP-HIGH WATER

10052

-

1

 

106

 

 

ROOM SENSOR FAILURE

 

 

10053

 

-

 

1

 

 

 

031

 

 

LOSS COMPRESSOR

10054

-

1

 

135

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

LOSS OF AIR BLOWER 1

 

 

10055

 

-

 

1

 

 

 

017

 

 

HUMIDIFIER LOW WATER

10058

-

1

 

153

 

 

HUMIDIFIER HIGH AMPS

 

 

10059

 

-

 

1

 

 

 

152

 

 

HIGH TEMPERATURE

10060

-

1

 

016

 

 

LOSS OF POWER

 

 

10061

 

-

 

1

 

 

 

142

 

 

UNSPECIFIED EVENT(S) [1]

10064

-

1

 

 

 

 

 

 

HIGH CW TEMP

 

 

10065

 

-

 

1

 

 

 

003

 

 

RESERVED

10066

-

1

 

005

 

 

HIGH ROOM TEMP

 

 

10067

 

-

 

1

 

 

 

018

 

 

LOW ROOM TEMP

10068

-

1

 

019

 

 

HIGH ROOM HUM

 

 

10069

 

-

 

1

 

 

 

020

 

 

LOW ROOM HUM

10070

-

1

 

021

 

 

HIGH TEMP SENSOR A

 

 

10071

 

-

 

1

 

 

 

022

 

 

LOW TEMP SENSOR A

10072

-

1

 

023

 

 

HIGH HUM SENSOR A

 

 

10073

 

-

 

1

 

 

 

024

 

 

LOW HUM SENSOR A

10074

-

1

 

025

 

 

LOSS OF CW FLOW

 

 

10075

 

-

 

1

 

 

 

004

 

 

CLOGGED FILTERS

10076

-

1

 

008

 

 

SUPPLY SENSOR FAILURE

 

 

10077

 

-

 

1

 

 

 

029

 

 

FREECOOL TEMP SENSOR

10078

-

1

 

 

062

 

30

Page 33
Image 33
Emerson OpenComms-485 manual Main FAN Overload