REV. 5 7/6/2007
Liebert Monitoring Group
Data Points Mapped to Input and Holding Registers
(A value read from an input register is the
Reference Document: ST100I&C PA Parameters and Events, Version 18.0
Data Description | Input Register | Holding Reg | # | Scale | Note | iCOM |
|
|
| Regs |
|
| Reference |
Vendor Id | 30001 | 40001 | 1 | 1 |
| - |
Device ID | 30002 | 40002 | 1 | 1 |
| - |
version number | 30003 | 40003 | 1 | 1 |
| - |
Ups/Env/Pwr | 30004 | 40004 | 1 | 1 |
| - |
Timer Mode[2] | 30016 | 40016 | 1 | 1 | .. | U609 |
Type of DT | 30017 | 40017 | 1 | 1 |
| S126 |
|
|
|
|
|
| |
Humidity Control | 30018 | 40018 | 1 | 1 |
| S114 |
Type [4] |
|
|
|
|
|
|
VSD Setpoint | 30019 | 40019 | 1 | 1 | % (HP) | S132 |
Supply | 30020 | 40020 | 1 | x10 | C° | U106 |
temperature Limit |
|
|
|
|
|
|
DT between | 30021 | 40021 | 1 | x10 | C° | S127 |
Room and FC |
|
|
|
|
|
|
Minimum CW | 30022 | 40022 | 1 | x10 | C° | S128 |
Temperature |
|
|
|
|
|
|
Temperature | 30023 | 40023 | 1 | x10 | C° | S102 |
Setpoint |
|
|
|
|
|
|
Temperature | 30024 | 40024 | 1 | x10 | C° | S104 |
proportional band |
|
|
|
|
|
|
Temperature | 30025 | 40025 | 1 | x10 | C° | S108 |
Dead band |
|
|
|
|
|
|
Temperature | 30026 | 40026 | 1 | 1 | Min | S105 |
Integration time |
|
|
|
|
|
|
Humidity Setpoint | 30027 | 40027 | 1 | 1 | % | S113 |
Humidity | 30028 | 40028 | 1 | 1 | % | S115 |
proportional band |
|
|
|
|
|
|
Humidity | 30029 | 40029 | 1 | 1 | Min | S116 |
Integration time |
|
|
|
|
|
|
Humidity Dead | 30030 | 40030 | 1 | 1 | % | S117 |
band |
|
|
|
|
|
|
Single unit Auto- | 30031 | 40031 | 1 | 1 | Sec | S417 |
restart Delay |
|
|
|
|
|
|
Infrared Flush | 30032 | 40032 | 1 | 1 | % | S414 |
Rate |
|
|
|
|
|
|
Temp Control | 30033 | 40033 | 1 | 1 |
| S103 |
Type [5] |
|
|
|
|
|
|
|
|
|
|
|
|
|
Sleep Interval 1 | 30040 | 40040 | 1 |
| MSB:Hr | U605(FROM) |
Start Time |
|
|
|
|
|
|
Hour:Minute |
|
|
|
|
|
|
Sleep Interval 1 | 30041 | 40041 | 1 |
| MSB:Hr | U605(TO) |
End Time |
|
|
|
|
|
|
32