REV. 5 7/6/2007

Liebert Monitoring Group –Development

Ambient Temperature

 

 

 

 

 

Warning Point

30069

40069

1

1

deg C

Over Temperature Limit

 

 

 

 

 

Point

30072

40072

1

1

deg C

Load (Apparent Power)

30102

 

2

1

VA

Load (Real Power)

30104

 

2

1

W

Load / Capacity

30106

 

1

1

%

Input Frequency

30107

 

1

10

Hz

Output Frequency

30108

 

1

10

Hz

Battery Charge Status

 

 

 

 

1 - 100% Charged

 

 

 

 

 

2 - Less than 100%

 

 

 

 

 

Charged

 

 

 

 

 

3 - Charging

 

 

 

 

 

4 - Discharging

 

 

 

 

 

5 - Float Charging

 

30112

 

1

 

6 - Equalize Charging

Battery Voltage

30113

 

1

1

V

Battery Time Remaining

30115

 

1

1

min

Battery Charge

 

 

 

 

 

Percentage

30116

 

1

1

%

Ambient Temperature

30119

 

1

1

deg C

Battery Test Result

30130

 

1

1

 

Input Voltage L1

30153

 

1

1

V

 

 

Input Current L1

30154

 

1

1

A

Output Voltage L1

30163

 

1

1

V

Output Current L1

30164

 

1

1

A

Input Maximum Voltage

30180

 

1

1

V

L1

 

Input Minimum Voltage

30181

 

1

1

 

L1

 

V

Output Maximum

30182

 

1

1

V

Voltage L1

 

Output Minimum

30183

 

1

1

 

Voltage L1

 

V

Black Out Count

30301

 

1

1

 

Brown Out Count

30302

 

1

1

 

17