REV. 5 7/6/2007 Liebert Monitoring Group –Development

Hardware

 

Load On Battery

10128

Output Off Pending

10151

Low Battery - Shutdown

10152

Imminent

Output Overload

10154

Over Temperature

 

Warning

10171

Input Power Supply Fail

10186

Input Over Voltage

10187

Input Under Voltage

10188

Input BrownOut

10189

Bad Input Frequency

10190

Output Under Voltage

10218

Output Over Voltage

10219

Charger Failed

10234

Battery Under Voltage

10241

Battery Over Voltage

10242

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

11

11

Data Point

 

 

 

 

 

Input Register

Holding Register

# of Reg.

Scale

Notes / Units

 

Number Of Input Lines

30004

40004

1

1

 

Bits 12 - 15

Number Of Output

 

 

 

 

 

Lines

30004

40004

1

1

Bits 8 - 11

Number Of SubModules

30009

40009

1

1

 

 

Load Circuit Present

 

 

 

 

There are 16 possible

 

 

 

 

 

Load Circuits. So each

 

 

 

 

 

bit represents 1 load

 

 

 

 

 

circuit. Load Circuit 1 is

 

 

 

 

 

bit 0, Load Circuit 2 is bit

 

 

 

 

 

1 and so on. If the bit is

 

 

 

 

 

1 then the Load Circuit

 

30013

40013

1

 

is supported.

Nominal Power Rating

30021

40021

2

1

 

VA

Nominal Input Voltage

30027

40027

1

1

V

Nominal Output Voltage

30028

40028

1

1

 

V

Nominal Input Current

30030

40030

1

1

A

Nominal Input

 

 

 

 

 

Frequency

30031

40031

1

10

Hz

Nominal Output

 

 

 

 

 

Frequency

30032

40032

1

10

Hz

Nominal Power Factor

30033

40033

1

100

 

 

Nominal Battery Voltage

30034

40034

1

1

V

Nominal Battery

 

 

 

 

 

Capacity

30037

40037

1

1

minutes

Nominal Battery Float

 

 

 

 

 

Voltage

30038

40038

1

1

V

Auto Restart Delay

30051

40051

1

1

 

seconds

Device Low Battery

 

 

 

 

 

Time

30053

40053

1

1

min

16

Page 19
Image 19
Emerson OpenComms-485 manual Data Point Input Register Holding Register # of Reg Scale