REV. 5 7/6/2007

 

 

 

 

Liebert Monitoring Group –Development

 

 

 

 

 

 

 

 

UPS Power Not Redundant

10296

 

1

 

1

 

 

Power Module Failure

10298

 

1

 

1

 

 

Battery Module Failure

10299

 

1

 

1

 

 

Power Module Warning

10300

 

1

 

1

 

 

Battery Module Warning

10301

 

1

 

1

 

 

Data Point

Input

Holding

# of

 

 

 

Register

Register

Reg.

Scale

Notes/ Units

 

Number Of Input Lines

30004

40004

1

 

1

Bits 12 - 15

 

Number Of Bypass Lines

30004

40004

1

 

1

Bits 4 - 7

 

Number Of Output Lines

30004

40004

1

 

1

Bits 8 - 11

 

Number Of Power Mod.

30010

40010

1

 

1

 

 

Number Of Battery Modules

30011

40011

1

 

1

 

 

Installed

 

 

 

Device Maximum Frame

30023

40023

2

 

1

 

 

Capacity

 

 

 

Device System Capacity

30025

40025

2

 

1

VA

 

Nominal Input Voltage

30027

40027

1

 

1

V

 

Nominal Output Voltage

30028

40028

1

 

1

V

 

Nominal Static Bypass

 

 

 

 

 

 

 

Switch Voltage

30029

40029

1

 

1

V

 

Nominal Input Frequency

30031

40031

1

 

10

Hz

 

Nominal Output Frequency

30032

40032

1

 

10

Hz

 

Nominal Power Factor

30033

40033

1

 

100

 

 

Nominal Battery Voltage

30034

40034

1

 

1

V

 

Auto Restart Delay

30051

40051

1

 

1

seconds

 

Device Auto Restart

30052

40052

1

 

1

%

 

Percent Setpt

 

 

Device Low Battery Time

30053

40053

1

 

1

min

 

Next Battery Auto Test

30057

40057

1

 

1

minutes

 

Time

 

 

Overload Alarm Limit

30067

40067

2

 

1

VA

 

Minimum Redundant Power

 

 

 

 

 

 

 

Modules

30074

40074

1

 

1

 

 

Load (Apparent Power)

30102

 

2

 

1

VA

 

Load (Real Power)

30104

 

2

 

1

W

 

Load / Capacity

30106

 

1

 

1

%

 

Input Frequency

30107

 

1

 

10

Hz

 

Output Frequency

30108

 

1

 

10

Hz

 

Bypass Frequency

30109

 

1

 

10

Hz

 

 

 

 

 

 

 

1 - 100% Charged

 

 

 

 

 

 

 

2 - Less than 100% Charged

 

 

 

 

 

 

 

3 - Charging

 

 

 

 

 

 

 

4 - Discharging

 

Battery Charge Status

30112

 

1

 

 

5 - Float Charging

 

 

 

 

6 - Equalize Charging

 

Battery Voltage

30113

 

1

 

1

V

 

Battery Time Remaining

30115

 

1

 

1

min

 

5

Page 8
Image 8
Emerson OpenComms-485 manual Input Holding Register Scale