REV. 5 7/6/2007
Liebert Monitoring Group
Free cooling run | 30146 | - | 1 | Hour | S505 |
hours |
|
|
|
|
|
Electrical Heaters | 30147 | - | 1 | Hour | S507 |
#1 run hours |
|
|
|
|
|
Electrical Heaters | 30148 | - | 1 | Hour | S508 |
#2 run hours |
|
|
|
|
|
Electrical Heaters | 30149 | - | 1 | Hour | S509 |
#3 run hours |
|
|
|
|
|
Hot Water / Hot | 30150 | - | 1 | Hour | S506 |
Gas run hours |
|
|
|
|
|
Daily High | 30151 | - | x10 | C° | S313 |
Temperature |
|
|
|
|
|
Daily High Temp | 30152 | - | x1 | Hh:mm | S313 |
Time |
|
|
|
|
|
Daily Low | 30153 | - | x10 | C° | S314 |
Temperature |
|
|
|
|
|
Daily Low Temp | 30154 | - | x1 | Hh:mm | S314 |
Time |
|
|
|
|
|
Daily High | 30155 | - | x1 | %RH | S315 |
Humidity |
|
|
|
|
|
Daily High Hum | 30156 | - | x1 | Hh:mm | S315 |
Time |
|
|
|
|
|
Daily Low | 30157 | - | x1 | %RH | S316 |
Humidity |
|
|
|
|
|
Daily Low Hum | 30158 | - | x1 | Hh:mm | S316 |
Time |
|
|
|
|
|
|
|
|
|
|
|
[1]Any
[2]Timer mode: 0 = no, 1= yes.
[3]Type of DT
[4]Predictive Hum Control: 0=relative, 1=compensated, 2=predictive.
[5]Temp Control Algorithm: 0=proportional, 1=PD, 2=PDI; 3=intelligent;
[6]When VFD is set to manual mode(coil 22), the host can control the VFD by the value of register 40019. The Manual VSD Timer will start to count down. Once it reaches 0, the VFD control mode will switch to auto. The host will need to periodically reset this timer in order to maintain the manual mode. Consult factory for BMS timer information.
[7]Operating State: Bit
Bit | ||
Bit | 0000 none, | |
| 0001 local user, | |
| 0010 alarm, | |
| 0011 schedule, | |
| 0100 remote user, | |
| 0101 external device, | |
| 0110 local display | |
[8] Alarm state bit map: | Bit0 =. Reset state | |
| bit1 = | Active state ; |
| bit2 = | Acknowledge state, |
00000: Message | |
| 00001: Warning |
| 00010: Alarm |
[9]