REV. 5 7/6/2007

Liebert Monitoring Group –Development

Battery Charge

 

 

 

 

1

- 100% Charged

Status

 

 

 

 

2

- Less than 100% Charged

 

 

 

 

 

3

- Charging

 

 

 

 

 

4

- Discharging

 

 

 

 

 

5

- Float Charging

 

30112

 

1

 

6

- Equalize Charging

 

 

 

 

 

Battery Voltage

30113

 

1

1

V

Battery Time

 

 

 

 

min

Remaining

30115

 

1

1

%

Battery Charge

30116

 

1

1

Percentage

 

 

 

Ambient

 

 

 

 

deg C

Temperature

30119

 

1

1

1

- Unknown

Battery Test

 

 

 

 

Result

 

 

 

 

2

- Passed

 

 

 

 

 

3

- Failed

 

 

 

 

 

4

- In Progress

 

 

 

 

 

5

- System Failure

 

30130

 

1

 

6

- Inhibited

 

 

 

 

 

Input Voltage L1

30153

 

1

1

V

Bypass Voltage L1

30159

 

1

1

V

Output Voltage L1

30163

 

1

1

V

Output Current L1

30164

 

1

1

A

Input Maximum

30180

 

1

1

V

Voltage L1

 

V

Input Minimum

 

 

 

 

Voltage L1

30181

 

1

1

 

 

Output Maximum

 

 

 

 

V

Voltage L1

30182

 

1

1

V

Output Minimum

30183

 

1

1

Voltage L1

 

 

 

Black Out Count

30301

 

1

1

 

 

Brown Out Count

30302

 

1

1

 

 

21

Page 24
Image 24
Emerson OpenComms-485 manual REV 7/6/2007 Liebert Monitoring Group -Development