REV. 5 7/6/2007
Liebert Monitoring Group
Input Phase Rotation | 10191 |
| 1 | 1 |
|
Error |
|
|
|
|
|
Bypass Phase Missing | 10201 |
| 1 | 1 |
|
Bypass Input Voltage | 10202 |
| 1 | 1 |
|
Fail |
|
|
|
|
|
Bypass Under Voltage | 10203 |
| 1 | 1 |
|
Fail |
|
|
|
|
|
Bypass Under Voltage | 10204 |
| 1 | 1 |
|
Warning |
|
|
|
|
|
Bypass Over Voltage | 10205 |
| 1 | 1 |
|
Fail |
|
|
|
|
|
Bypass Over Voltage | 10206 |
| 1 | 1 |
|
Warning |
|
|
|
|
|
Output Under Voltage | 10218 |
| 1 | 1 |
|
Output Over Voltage | 10219 |
| 1 | 1 |
|
Output Short Circuit | 10220 |
| 1 | 1 |
|
Module with Active | 10304 |
| 1 | 1 |
|
Alarm |
|
|
|
|
|
Data Point | Input | Holding | # of | Scale | Notes / Units |
| Register | Register | Reg. |
|
|
Number Of Input Lines | 30004 | 40004 | 1 | 1 | Bits 12 - 15 |
Number Of Bypass | 30004 | 40004 | 1 | 1 | Bits 4 - 7 |
Lines |
|
|
|
|
|
Number Of Output | 30004 | 40004 | 1 | 1 | Bits 8 - 11 |
Lines |
|
|
|
|
|
Number Of Sub- | 30009 | 40009 | 1 | 1 |
|
Modules |
|
|
|
|
|
Nominal Power Rating | 30021 | 40021 | 2 | 1 | VA |
Nominal Input Voltage | 30027 | 40027 | 1 | 1 | V |
Nominal Output | 30028 | 40028 | 1 | 1 | V |
Voltage |
|
|
|
|
|
Nominal Static Bypass | 30029 | 40029 | 1 | 1 | V |
Switch Voltage |
|
|
|
|
|
Nominal Input Current | 30030 | 40030 | 1 | 1 | A |
Nominal Output | 30032 | 40032 | 1 | 10 | Hz |
Frequency |
|
|
|
|
|
Nominal Power Factor | 30033 | 40033 | 1 | 100 |
|
Nominal Battery | 30034 | 40034 | 1 | 1 | V |
Voltage |
|
|
|
|
|
Load (Apparent | 30102 |
| 2 | 1 | VA |
Power) |
|
|
|
|
|
Load (Real Power) | 30104 |
| 2 | 1 | W |
Load / Capacity | 30106 |
| 1 | 1 | % |
Output Frequency | 30108 |
| 1 | 10 | Hz |
Bypass Frequency | 30109 |
| 1 | 10 | Hz |
Battery Charge Status | 30112 |
| 1 |
| 1 - 100% Charged |
|
|
|
|
| 2 - Less than 100% Charged |
|
|
|
|
|
|
Battery Voltage | 30113 |
| 1 | 1 | V |
Battery Current | 30114 |
| 1 | 1 | A |
Battery Time | 30115 |
| 1 | 1 | min |
Remaining |
|
|
|
|
|
Battery Charge | 30116 |
| 1 | 1 | % |
Percentage |
|
|
|
|
|
24