REV. 5 7/6/2007
Liebert Monitoring Group
Liebert HiNet
Supported Modbus Points
Data Point | Status | Coil | # of Reg. | Scale | Notes / Units | |
10042 |
| 1 | 1 |
| ||
Load On Inverter | 10073 |
| 1 | 1 |
| |
Bypass Active | 10074 |
| 1 | 1 |
| |
Load On Battery | 10128 |
| 1 | 1 |
| |
Permanently On Bypass | 10133 |
| 1 | 1 |
| |
Bypass SCR Open Circuit | 10149 |
| 1 | 1 |
| |
Low Battery - Shutdown | 10152 |
| 1 | 1 |
| |
Imminent |
|
| ||||
Output Overload | 10154 |
| 1 | 1 |
| |
Inverter Unsynchronized | 10160 |
| 1 | 1 |
| |
Input Power Supply Fail | 10186 |
| 1 | 1 |
| |
Bypass Input |
|
|
|
|
| |
Voltage/Frequency Fault | 10202 |
| 1 | 1 |
| |
Data Point | Input | Holding |
|
| Notes / Units | |
Register | Register | # of Reg. | Scale | |||
Number Of Input Lines | 30004 | 40004 | 1 | 1 | Bits 12 - 15 | |
Number Of Bypass Lines | 30004 | 40004 | 1 | 1 | Bits 4 - 7 | |
Number Of Output Lines | 30004 | 40004 | 1 | 1 | Bits 8 - 11 | |
Number Of SubModules | 30009 | 40009 | 1 | 1 |
| |
Number Of Battery Cells | 30012 | 40012 | 1 | 1 |
| |
Load Circuit Present |
|
|
|
| There are 16 possible Load | |
|
|
|
|
| Circuits. So each bit | |
|
|
|
|
| represents 1 load circuit. | |
|
|
|
|
| Load Circuit 1 is bit 0, Load | |
|
|
|
|
| Circuit 2 is bit 1 and so on. | |
| 30013 | 40013 | 1 |
| If the bit is 1 then the Load | |
|
| Circuit is supported. | ||||
Load (Apparent Power) | 30102 |
| 2 | 1 | VA | |
Load (Real Power) | 30104 |
| 2 | 1 | W | |
Input Frequency | 30107 |
| 1 | 10 | Hz | |
Output Frequency | 30108 |
| 1 | 10 | Hz | |
Battery Voltage | 30113 |
| 1 | 1 | V | |
Battery Current | 30114 |
| 1 | 1 | A | |
(Charge/Discharge) |
|
| ||||
Battery Charge Percentage | 30116 |
| 1 | 1 | % | |
Ambient Temperature | 30119 |
| 1 | 1 | deg C | |
Input Voltage L1 | 30153 |
| 1 | 1 | V | |
Input Current L1 | 30154 |
| 1 | 1 | A | |
Output Voltage L1 | 30163 |
| 1 | 1 | V | |
Output Current L1 | 30164 |
| 1 | 1 | A | |
Input Voltage L2 | 30203 |
| 1 | 1 | V | |
|
|
|
|
|
|