REV. 5 7/6/2007

Liebert Monitoring Group –Development

Modbus Packet Format

Each Modbus packet consists of the following fields:

Device Address

Function Code

Data Field(s)

Error Check Field

Device Address:

The address field immediately follows the beginning of the frame and consists of 8-bits (RTU). This bit indicates the user assigned address of the slave device that is to receive the message sent by the attached master device.

Each slave must be assigned a unique address and only the addressed slave will respond to a query that contains its address.

Function Code:

The function code field tells the addressed slaves what function to perform. Function codes are specifically designed invoke a specific action by the slave device. The function code range is from 1 to 127.

OC-485 Modbus server supports the following Modbus function codes.

 

Code

Function

Description

 

 

01

Read Coils

Read from 1 to 2000 contiguous status of coils managed

 

 

 

 

by the server. Coils in the response message are packed

 

 

 

 

as one per bit of a byte, 1=ON and 0=OFF. If the

 

 

 

 

requested quantity of coils is not a multiple of 8, zeros

 

 

 

 

are padded in the final byte.

 

 

02

Read Discrete

Read from 1 to 2000 contiguous status of input status

 

 

 

Inputs

managed by the server. Discrete inputs in the response

 

 

 

 

message are packed as one per bit of a byte, 1=ON and

 

 

 

 

0=OFF. If the requested quantity of inputs is not a

 

 

 

 

multiple of 8, zeros are padded in the final byte.

 

 

03

Read Holding

Read the contents of contiguous block of 1 to 127

 

 

 

Registers

holding registers. Data are packed as two bytes per

 

 

 

 

register; the first byte contains the high order bits.

 

 

04

Read

Read the contents of contiguous block of 1 to 127 input

 

 

 

InputRegisters

registers. Data are packed as two bytes per register; the

 

 

 

 

first byte contains the high order bits.

 

 

05

Write Single Coil

Write a single output to either ON(1) or OFF(0) mapped

 

 

 

 

in coil section.

 

 

06

Write Single

Write a value into a single holding register;

 

 

 

Register

 

 

 

15

Write Multiple

Force each coil in a sequence of coils to either ON or

 

 

 

Coils

OFF.

 

 

 

 

 

 

 

 

 

2

 

Page 5
Image 5
Emerson OpenComms-485 manual Modbus Packet Format