REV. 5 7/6/2007

Liebert Monitoring Group –Development

Liebert PowerSure Interactive 2

Supported Modbus Points

Data Point

 

 

 

 

 

 

 

 

 

 

Status

Coil

# of Reg.

Scale

Notes / Units

 

Audible Alarm Enabled

10002

2

1

1

 

 

Automatic Battery Test

 

 

 

 

 

Enabled

10003

3

1

1

 

DC-To-DC Converter

 

 

 

 

 

On

10042

 

1

1

 

Battery Charger On

10044

 

1

1

 

Load Circuit 1 State

10057

 

1

1

 

Load Circuit 2 State

10058

 

1

1

 

Load Circuit 3 State

10059

 

1

1

 

Load Circuit 4 State

10060

 

1

1

 

Load Circuit 5 State

10061

 

1

1

 

Load Circuit 6 State

10062

 

1

1

 

Load Circuit 7 State

10063

 

1

1

 

Load Circuit 9 State

10065

 

1

1

 

Load Circuit 10 State

10066

 

1

1

 

Load Circuit 11 State

10067

 

1

1

 

Load Circuit 12 State

10068

 

1

1

 

Load Circuit 13 State

10069

 

1

1

 

Load Circuit 14 State

10070

 

1

1

 

Load Circuit 15 State

10071

 

1

1

 

Load Circuit 16 State

10072

 

1

1

 

Load On Inverter

10073

 

1

1

 

Boost Mode On

10075

 

1

1

 

Buck Mode On

10076

 

1

1

 

Replace Battery

10081

 

1

1

 

Battery Under Test

10082

 

1

1

 

Shutdown Reason -

 

 

 

 

 

Over Temperature

10086

 

1

1

 

 

 

Shutdown Reason -

 

 

 

 

 

Overload

10087

 

1

1

 

Shutdown Reason -

 

 

 

 

 

Output Short

10089

 

1

1

 

Shutdown Reason -

 

 

 

 

 

Line Neutral Swap

10090

 

1

1

 

Shutdown Reason -

 

 

 

 

 

Low Battery

10092

 

1

1

 

Shutdown Reason -

 

 

 

 

 

Remote Shutdown

10093

 

1

1

 

Shutdown Reason -

 

 

 

 

 

Input Under Voltage

10094

 

1

1

 

 

 

Shutdown Reason -

10096

 

1

1

 

15

Page 18
Image 18
Emerson OpenComms-485 manual Supported Modbus Points