REV. 5 7/6/2007
Liebert Monitoring Group
Liebert UPS Series 300
Supported Modbus Points
Data Point | Status | Coil | # of | Scale | Notes / Units |
|
|
| Reg. |
|
|
Automatic Restart | 10001 | 1 | 1 | 1 |
|
Enabled |
|
|
|
|
|
Battery Charge | 10046 |
| 1 | 1 |
|
Compensation |
|
|
|
|
|
Inverter Ready | 10047 |
| 1 | 1 |
|
Load Circuit 1 State | 10057 |
| 1 | 1 |
|
Load Circuit 2 State | 10058 |
| 1 | 1 |
|
Load Circuit 3 State | 10059 |
| 1 | 1 |
|
Load Circuit 4 State | 10060 |
| 1 | 1 |
|
Load Circuit 5 State | 10061 |
| 1 | 1 |
|
Load Circuit 6 State | 10062 |
| 1 | 1 |
|
Load Circuit 7 State | 10063 |
| 1 | 1 |
|
Load Circuit 8 State | 10064 |
| 1 | 1 |
|
Load Circuit 9 State | 10065 |
| 1 | 1 |
|
Load Circuit 10 State | 10066 |
| 1 | 1 |
|
Load Circuit 11 State | 10067 |
| 1 | 1 |
|
Load Circuit 12 State | 10068 |
| 1 | 1 |
|
Load Circuit 13 State | 10069 |
| 1 | 1 |
|
Load Circuit 14 State | 10070 |
| 1 | 1 |
|
Load Circuit 15 State | 10071 |
| 1 | 1 |
|
Load Circuit 16 State | 10072 |
| 1 | 1 |
|
Load On Inverter | 10073 |
| 1 | 1 |
|
Bypass Active | 10074 |
| 1 | 1 |
|
Buck On | 10076 |
| 1 | 1 |
|
Replace Battery | 10081 |
| 1 | 1 |
|
Battery Under Test | 10082 |
| 1 | 1 |
|
Load On Battery | 10128 |
| 1 | 1 |
|
Low Battery - | 10152 |
| 1 | 1 |
|
Shutdown Imminent |
|
|
|
|
|
Output Overload | 10154 |
| 1 | 1 |
|
Over Temperature | 10171 |
| 1 | 1 |
|
Warning |
|
|
|
|
|
Battery Over | 10172 |
| 1 | 1 |
|
Temperature CB Trip |
|
|
|
|
|
Input Power Supply | 10186 |
| 1 | 1 |
|
Fail |
|
|
|
|
|
Input Over Voltage | 10187 |
| 1 | 1 |
|
Input Under Voltage | 10188 |
| 1 | 1 |
|
Bad Input Frequency | 10190 |
| 1 | 1 |
|
Bypass Input | 10202 |
| 1 | 1 |
|
Voltage/Frequency |
|
|
|
|
|
Fault |
|
|
|
|
|
Output Under Voltage | 10218 |
| 1 | 1 |
|
Output Over Voltage | 10219 |
| 1 | 1 |
|
26