Emerson OpenComms-485 manual REV 7/6/2007 Liebert Monitoring Group -Development

Models: OpenComms-485

1 39
Download 39 pages 12.67 Kb
Page 9
Image 9

REV. 5 7/6/2007

Liebert Monitoring Group –Development

Battery Charge Percentage

30116

 

1

1

%

Battery Temperature

30117

 

1

1

deg C

Transformer Temperature

30121

 

1

1

deg C

Redundant Power Modules

30124

 

1

1

 

Active Power Module Count

30126

 

1

1

 

Battery Module Active

 

 

 

 

 

Count

30127

 

1

1

 

Battery Test Result

30130

 

1

1

 

Input Voltage L1

30153

 

1

1

V

Input Current L1

30154

 

1

1

A

Bypass Voltage L1

30159

 

1

1

V

Bypass Current L1

30160

 

1

1

A

Output Voltage L1

30163

 

1

1

V

Output Current L1

30164

 

1

1

A

Power Module Failure

 

 

 

 

 

Count

30304

 

1

1

 

Battery Module Failure

 

 

 

 

 

Count

30305

 

1

1

 

Power Module Warning

30306

 

1

1

 

Count

 

 

Battery Module Warning

30307

 

1

1

 

Count

 

 

6

Page 9
Image 9
Emerson OpenComms-485 manual REV 7/6/2007 Liebert Monitoring Group -Development