REV. 5 7/6/2007

Liebert Monitoring Group –Development

Liebert Nfinity

Supported Modbus Points

Data Point

Status

Coil

# of

Scale

Notes/ Units

Reg.

Automatic Battery Test

10003

3

1

1

 

Enabled

 

Battery Charger On

10044

 

1

1

 

Inverter Ready

10047

 

1

1

 

Power Factor Correction

 

 

 

 

 

State

10050

 

1

1

 

Load On Inverter

10073

 

1

1

 

Bypass Active

10074

 

1

1

 

Replace Battery

10081

 

1

1

 

Battery Under Test

10082

 

1

1

 

Load On Battery

10128

 

1

1

 

Load On Bypass

10129

 

1

1

 

Load On Manual Bypass

10132

 

1

1

 

Load Transferred To

10134

 

1

1

 

Bypass Due To UPS Fault

 

 

Transfer Inhibit

10146

 

1

1

 

Output Off Pending

10151

 

1

1

 

Low Battery - Shutdown

 

 

 

 

 

Imminent

10152

 

1

1

 

Output Overload

10154

 

1

1

 

UPS Overload

10155

 

1

1

 

Output Off

10158

 

1

1

 

Check Air Filter - Replace

10170

 

1

1

 

Transformer Over

10178

 

1

1

 

Temperature

 

 

Input Power Supply Fail

10186

 

1

1

 

Internal Device

 

 

 

 

 

Communication Failure

10284

 

1

1

 

Device Active Alarm

10290

 

1

1

 

Main Control Warning

10291

 

1

1

 

Redundant Control Warning

10292

 

1

1

 

Control Module Failure

10293

 

1

1

 

Redundant Control Module

 

 

 

 

 

Failed

10294

 

1

1

 

User Interface Module

 

 

 

 

 

Failed

10295

 

1

1

 

4

Page 7
Image 7
Emerson OpenComms-485 manual Liebert Nfinity, Status Coil Scale Reg