Danfoss Liquid Injection Valve Setup

Danfoss Liquid Injection Valve Setup

ICM/ICAD Motorized Valve Setup Instructions

The following items need to be setup in order for the valve to operate properly.

1.Press the “Circle” button on the valve. A value of “01” should be shown on the screen.

2.Press the “Circle” button. There should be a value of “1” shown. If not use the up/down arrows to change it to the correct value. Press the “Circle” button when done.

3.Press the “Up” arrow button. A value of”02” should be shown on the screen.

4.Press the “Circle” button. There should be a value of “1” shown. If not use the up/down arrow buttons to change it to the correct value. Press the “Circle” button when done.

5.Press the “Up” arrow button. A value of “03” should be shown on the screen.

6.Press the “Circle” button. There should be a value of “2” shown. If not, use the up/down arrow buttons to change it to the correct value. Press the “Circle” button when done.

7.Press the “Up” arrow button until a value of “04” is shown on the screen.

8.Press the “Circle” button. There should be a value of “50” shown. If not, use the up/down arrow buttons to change it to the correct value. Press the “Circle” button when done.

9.Press the “Up” arrow button until a value of “07” is shown on the screen.

10.Press the “Circle” button. There should be a value of “1” shown. If not, use the up/down arrow buttons to change it to the correct value. Press the “Circle” button when done.

11.Press the “Up” arrow button until a value of “10” is shown on the screen.

12.Press the “Circle” button. Press the up/down arrow button to change the value to “11”. Press the “Circle” button.