Wiring the ICAD

ICM/ICAD Motorized Valve

Installation, Programming, and Troubleshooting

 

 

Wiring the ICAD

Note: The ICAD is powered by a 24 Volt DC power source.

 

There are two cables pre-mounted and connected to the ICAD motor actuator. Never try to

 

open the ICAD motor because the special moisture seal will be damaged.

The power cable consists of 3 wires:

Green: (–) common (ground)

Brown: (+) positive from 24VDC power source

White: (+) positive from UPS/battery backup (optional)

The control cable consists of 7 wires:

Yellow:

(–) common (ground)

Gray:

(+) positive 4-20mA or 0-20mA input to control ICAD motor

Blue:

(+) positive 4-20mA or 0-20mA output from ICAD for valve

 

 

position feedback

Pink:

(+) positive 2-10V or 0-10V input to control ICAD motor. Also used as a

 

 

digital input with the yellow wire for on/o! solenoid valve operation.

White: common alarm (digital NPN transistor output when combined with yellow wire)

Brown: indicates ICM is fully open (digital NPN transistor output when combined with yellow wire)

Green: indicates ICM is fully closed (digital NPN transistor output when combined with yellow wire)

Electrical Data

Supply voltage is galvanically isolated from input and output wires.

Supply voltage

24 V d.c., +10% / -15% Load ICAD 600: 1.2 A ICAD 900: 2.0 A

Fail safe supply

Min. 19 V d.c.

Load ICAD 600: 1.2 A

ICAD 900: 2.0 A

Anolog input - Current or Voltage

Current

0/4 - 20 mA Load: 200 Ω

Voltage

0/2 - 10 V d.c. Load: 10 kΩ

Analog output 0/4 - 20 mA Load: ≤ 250 Ω

Digital input - Digital ON/OFF input by means of voltfree contact (Signal/Telecom relays with gold-plated contacts recommended) – Voltage input used

ON: contact impedance < 50 Ω)

OFF: contact impedance > 100 kΩ

Digital output - 3 pcs. NPN transistor output

External supply: 5 -

24 V d.c. (same supply as for ICAD can be used, but please note that the

 

galvanically isolated system will then be spoiled).

Output load:

50

Ω

Load:

Max. 50 mA

Danfoss (USCO / MKS), 11 - 2006

DKRCI.EI.HT0.A1.22 / 520H1639

5