45
Users Manual
By contrast, many meters use
Effects of Internal Noise in AC Measurements
With the input shorted in an ac function (volts ac, current ac, or frequency) the display will read approximately 50 due to internal amplifier noise. Because the meter is a true rms responding meter, this noise has only minimal contribution to the reading at the specified floor (1500 counts in the medium rate) of each range. When the rms value of the two signals (internal noise and range floor) is calculated, the effect of the noise is shown:
Total rms digits = (502 + 1500 2 ) = 1500.8
The display will read 1501. At the
Note
Do not use the relative modifier (REL) to "zero" the meter because the relative reading is simply subtracted from the present reading.
Calculated (AC + DC) RMS Measurements
When Yand Z, or Cand Dare pressed simultaneously, the meter will alternately take a dc and an ac measurement then calculate and display the rms value:
RMS value = dc 2 + ac 2
In the dual display mode, when the volts ac and volts dc functions are selected, the 10 MΩ dc input divider is in parallel with the
Note
When measuring AC + DC, (or any dual display combination of AC and DC) In the fast reading rate, the Fluke 45 may show significant reading errors. This results from a lack of filtering on the DC portion of the measurement for the fast reading rate. To avoid this problem, use only the "slow" and "medium" reading rates for AC + DC or AC and DC combinations.
Waveform Comparison (True RMS vs.
Figure
Since