D. Install Attic Insulation Shield

WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home Technologies Inc. requires the use of an attic shield.

The National Fuel Gas Code ANSI Z223.1 requires an at- tic shield constructed of 26 gauge minimum metal that ex- tends at least 2 in. (51 mm) above insulation.

Attic shields must meet specified clearance and be se- cured in place.

Flat Ceiling Installation

Remove one shield from box.

Note: Cut previously installed batt insulation to make room for the attic insulation shield.

• Wrap shield around pipe if pipe is already installed in

area to be insulated.

• Match the three holes in each side and fasten with three

screws to form a tube.

• Bend three tabs on the bottom of the shield outward to

allow attachment to the ceiling firestop.

• Bend the remaining tabs inward 90° to maintain the air

Bend all tabs inward 90° to maintain clearance and prevent insulation from falling inside.

Insert 3 screws

Laser-etched cut lines

Bend 3 tabs outward to fasten to ceiling firestop - bend remaining tabs inward 90° to maintain clearance

space between the pipe and the shield. Set the shield

on the ceiling firestop and attach to the firestop.

• Bend all tabs inward 90° around the top of the shield.

These tabs must be used to prevent blown insulation

from getting between the shield and vent pipe, and to

maintain air space clearance.

Vaulted Ceiling Installation

The attic insulation shield has been laser-etched with cut lines and ceiling pitches to make field trimming easier.

Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Ε Cut the attic insulation shield (if application is for vaulted ceiling) using a laser-etched cut line, to fit your ceiling pitch. Snip cut edge to create 1 in. bend tabs.

Wrap shield around pipe if pipe is already installed in area to be insulated.

Match the three holes in each side and fasten with three screws to form a tube.

Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling firestop.

Bend the remaining tabs inward 90° to maintain the air space between the pipe and the shield. Set the shield on the ceiling firestop and attach to the firestop.

Bend all tabs inward 90° around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.

Figure 8.5 Attic Insulation Shield

Heatilator • Novus NDV Series • 4055-187 Rev F • 06/08

35

Page 35
Image 35
Hearth and Home Technologies NDV4236IL, NDV3630, NDV3933L Install Attic Insulation Shield, Flat Ceiling Installation