Hearth and Home Technologies NDV4842IL, NDV4236IL, NDV3630 5 Minimum Clearances for Terminations

Models: NDV3933IL NDV3036IL NDV4236L NDV4842L NDV4236I NDV3933L NDV4236IL NDV4842 NDV3630L NDV3933I NDV4842IL NDV4236 NDV4842I NDV3630 NDV3933 NDV3630I

1 84
Download 84 pages 46.5 Kb
Page 22
Image 22
Figure 6.5 Minimum Clearances for Terminations

D

E

Manual background V Manual background

LManual backgroundManual backgroundManual backgroundBManual backgroundManual background C Manual background

V

Fixed

Closed

 

Manual backgroundF Manual backgroundV

Manual background B Manual background

H

O Manual background

N

V

Manual background B Manual backgroundV

VOpenable Fixed Closed

 

V

 

B

B

J

X

 

 

 

 

 

A

GAS METER

 

 

 

 

 

 

G

 

 

 

V

 

M

 

V

I

V

K X

 

 

A

V TERMINATION CAP

Measure vertical clearances from this surface

T

X AIR SUPPLY INLET

Q P

Manual backgroundManual backgroundManual backgroundVManual backgroundManual backgroundManual background

R

S

RESTRICTION ZONE (TERMINATION NOT ALLOWED)

V Manual background U

V

W

Electrical Service

D*

V

U

V

Measure horizontal clearances

Covered Alcove

Applications

from this surface.

 

Clearances to Electrical Service

Dimension Descriptions

AClearance above the ground, a veranda, porch, deck or balcony - 12 in. (30 cm) minimum. *

BClearance to window or door that may be opened – 10,000 BTUs or less, 6 in. (15 cm) minimum; 10,000-50,000 BTUs, 9 in. (23 cm) minimum; over 50,000 BTUs, 12 in. (30 cm) minimum. *

CClearance to permanently closed window – 12 in. (30 cm) minimum - recommended to prevent condensation on window.

DVertical clearance to ventilated soffit located above the termination within a horizontal distance of 2 ft (60 cm) from the centerline of the termination – 18 in. (46 cm) minimum. **

EVertical clearance to unventilated soffit - 12 in. (30 cm) minimum. **

FClearance to outside corner - 6 in. (15 cm) minimum.

GClearance to inside corner - 6 in. (15 cm) minimum.

HNot to be installed above a meter/regulator assembly within 3 ft (90 cm) horizontally* from the center line of the regulator (Canada only)

IClearance to service regulator vent outlet – 3 ft (.91 m) U.S. minimum and 3 ft (.91 m) Canada minimum. *

JClearance to non-mechanical air supply inlet into building or the combustion air inlet to any other appliance – 9” (23 cm) U.S. minimum and 12 in. (30 cm) Canada minimum. *

KClearance to mechanical air supply inlet - 3 ft (.91 m) U.S. minimum and 6 ft (1.8 m) Canada minimum. *

LClearance above a paved sidewalk or paved driveway located on public property - 7 ft (2.1 m) minimum.

A vent may not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

MClearance under veranda, porch, deck or balcony - 12 in. (30 cm) minimum. * Recommended 30 in. (76 cm) for vinyl or plastic.

Only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor. *

NVertical clearance between two horizontal termination caps – 12 in. (30 cm) minimum.

Figure 6.5 Minimum Clearances for Terminations

OHorizontal clearance between two horizontal termination caps – 12 in. (30 cm) minimum.

P6” - Non-vinyl sidewalls 12” – Vinyl sidewalls

Q18” – Non-vinyl soffit and overhang 42” – Vinyl soffit and overhang

 

 

S min

T max

1 cap

 

3 ft

2 x S actual

2 caps

 

6 ft

1 x S actual

3 caps

 

9 ft

2/3 x S actual

4 caps

 

12 ft

1/2 x S actual

S min = # term caps x 3

T max = (2/# term caps) x S (actual)

R 8 ft.

U6” min. – Clearance from sides of electrical service. W 12” min. – Clearance above electrical service.

* As specified in CGA B149 Installation Codes

Note: Local codes or regulations may require different clearances. ** Clearance required to vinyl soffit material – 30 in. (76 cm) minimum.

Note: Location of the vent termination must not interfere with access to the electrical service.

WARNING!

In the U.S.: Vent system termination is NOT permitted in screened porches. You must follow side wall, overhang and ground clearances as stated in the instructions.

In Canada: Vent system termination is NOT permitted in screened porches. Vent system termination is permitted in porch areas with two or more sides open. You must follow all side wall, overhang and ground clearances as stated in the instructions.

Hearth & Home Technologies assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.

CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.

22

Heatilator • Novus NDV Series • 4055-187 Rev F • 06/08

Page 22
Image 22
Hearth and Home Technologies NDV4842IL, NDV4236IL, NDV3630, NDV3933L, NDV4842L, NDV4236L 5 Minimum Clearances for Terminations