ÎL. Install Heat Shields and Horizontal Termi-
nation Cap
Note: For installations using black pipe, slide the decorative wall thimble over the last vent pipe before connecting the termination
cap to the pipe. When this connection has been made, slide the wall thimble up to the interior wall surface and attach with screws provided. See figure 10.25
Figure 10.25 Wall Thimble
Heat Shield Requirements for Horizontal Termi- nation
For all horizontally vented appliances, a heat shield MUST be placed one in. above the top of the vent be- tween the wall shield firestop and the base of the termina- tion cap.
There are two sections of the heat shield. One section is
If the wall thickness does not allow the required
WARNING! Risk of Fire! To prevent overheating and fire, heat shields must extend through the entire wall thickness. Heat shields must overlap
•DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap (shown in Figure 10.26).
•If the wall thickness is less than 4 in./102 mm (DVP) or
•Use an extended heat shield if the finished wall thickness is greater than
•The extended heat shield may need to be cut to length maintaining sufficient length for a
•Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield.
•Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section.
Important Notice: Heat shields may not be field constructed.