Heat & Glo LifeStyle 6000 ARCH, 8000 DVTFL, SL-42 DVT manual Round and Trapezoid Termination Caps

Models: 8000 DVTFL 6000 XLT 6000 ARCH 6000 DVTFL SL-42 DVT

1 46
Download 46 pages 22.06 Kb
Page 27
Image 27
Figure 24. Round and Trapezoid Termination

For round cap termination:

1. Secure the pipe, using the exterior pipelock hole on the round flange of the wall firestop.

For trapezoidal termination:

1.Screw the cap to the exterior wall through the flanges in the cap.

2.Seal the joint between the pipe and the

exterior firestop.

Figure 24. Round and Trapezoid Termination

Caps

WARNING

THE BOTTOM OF THE VENT

TERMINATION CAP MUST BE A

MINIMUM OF 12 INCHES (305 MM)

ABOVE GROUND LEVEL (GRADE). THE

TOP OF THE CAP MUST BE A MINIMUM

OF 18 INCHES (457 MM) BELOW

COMBUSTIBLE MATERIAL, SUCH AS A

DECK, AND THE SIDE OF THE CAP

MUST BE A MINIMUM OF 6 INCHES (152

MM)AWAY FROM A PARALLEL OUTSIDE WALL. VENTING TERMINALS SHALL NOT BE RECESSED INTO A WALL OR SIDING. SEE THE FOLLOWING DIAGRAM FOR VENT TERMINATION CLEARANCES.

24

Page 27
Image 27
Heat & Glo LifeStyle 6000 ARCH, 8000 DVTFL, SL-42 DVT, 6000 XLT, 6000 DVTFL manual Round and Trapezoid Termination Caps