Heat & Glo LifeStyle SL-42 DVT, 8000 DVTFL Step Positioning Leveling, and Securing the, Fireplace

Models: 8000 DVTFL 6000 XLT 6000 ARCH 6000 DVTFL SL-42 DVT

1 46
Download 46 pages 22.06 Kb
Page 31
Image 31
Step 4

Step 4

Positioning,

Leveling, and

Securing the

Fireplace

1.Place the fireplace into position.

2.Level the fireplace from side to side and from front to back.

3.Shim the fireplace with non-combus- tible material, such as sheet metal, as necessary.

4.Secure the fireplace to the framing by nailing or screwing

Step 5

The Gas Control

Systems

The diagram below shows how to properly position, level, and secure the fireplace.

Figure 27. Proper Positioning, Leveling, and

Securing of a Fireplace

WARNING

THIS UNIT IS NOT FOR USE WITH

SOLID FUEL.

Two types of gas control systems are used with these models: Standing Pilot Ignition and Direct Spark Ignition (DSI). Model 6000XLT has Standing Pilot Ignition only. Model 6000ARCH has DSI only.

Standing Pilot Ignition System

This system includes millivolt control valve, standing pilot, thermopile/thermocouple flame sensor, and piezo ignitor.

WARNING

110-120 VAC MUST NEVER BE CONNECTED TO A CONTROL VALVE IN A MILLIVOLT SYSTEM.

Direct Spark Ignition (DSI) System

This system includes a 24V control valve, electronic module, transformer, and spark ignitor/flame sensor.

WARNING

110-120 VAC MUST BE WIRED TO THE FIREPLACE JUNCTION BOX IN A DSI SYSTEM.

WARNING

DIRECT VENT PROPANE MODELS WITH DSI CONTROL SYSTEMS CANNOT BE USED IN CANADA.

28

Page 31
Image 31
Heat & Glo LifeStyle SL-42 DVT manual Step Positioning Leveling, and Securing the, Fireplace, Step The Gas Control Systems