Heatiator HEIR36H, HEIR42H, HEIR42T, HEIR50T D. Mantel and Wall Projections, Non-CombustibleZone

Models: HEIR50H HEIR36T HEIR36H HEIR50T HEIR42T HEIR42H

1 79
Download 79 pages 1.16 Kb
Page 21
Image 21
Non-Combustible Zone

Non-Combustible Zone

1/2 IN. BUILDING MATERIAL

PIPE IS FOR VISUAL

(MAY BE COMBUSTIBLE)

 

REFERENCE ONLY

NO COMBUSTIBLES

 

IN HATCHED AREA

 

1 IN.

 

 

39 IN.

FACTORY-SUPPLIED

 

1/2 IN.

 

NON-COMBUSTIBLE

 

BOARD

 

= COMBUSTIBLES

NOT ALLOWED

Figure 5.3 Allowable Combustible Mantel Projections

D. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear- ances as specified. Framing or finishing material closer than the minimums listed must be constructed entirely of non- combustible materials (i.e., steel studs, concrete board, etc).

When installing a mantel, provisions must be made in order to secure the mantel to the adjacent framing materials. For example, lintel brackets or lag bolts may be considered for this purpose.

Combustible Mantel Legs or Wall Projections

1/2 IN. BUILDING MATERIAL

COMBUSTIBLE

COLUMN

 

4 IN.

 

7 IN.

FIREPLACE

14 IN.

OPENING

 

FACTORY-SUPPLIED

 

NON-COMBUSTIBLE BOARD

 

COMBUSTIBLE OR

NON-COMBUSTIBLE WALL

Figure 5.4 Combustible Mantel Leg and Wall Projections

Non-Combustible Mantel Legs or Wall Projections

 

1/2 IN. BUILDING MATERIAL

 

NON-COMBUSTIBLE

 

COLUMN

 

6 IN. MAX.

 

SEE SECTION 13.E

 

FOR REQUIRED

FIREPLACE

CLEARANCES

OPENING

14 IN. MIN.

 

FACTORY-SUPPLIED

 

NON-COMBUSTIBLE

COMBUSTIBLE OR

BOARD

NON-COMBUSTIBLE

 

 

WALL

Figure 5.5 Non-Combustible Mantel Leg and Wall Projections

Heatilator • HEIR36, HEIR42, HEIR50 • 2285-900 Rev. D • 8/12

21

Page 21
Image 21
Heatiator HEIR36H D. Mantel and Wall Projections, Non-CombustibleZone, Combustible Mantel Legs or Wall Projections