Heatiator HEIR50H, HEIR42H, HEIR42T B. Secure the Vent Sections, C. Disassemble Vent Sections

Models: HEIR50H HEIR36T HEIR36H HEIR50T HEIR42T HEIR42H

1 79
Download 79 pages 1.16 Kb
Page 41
Image 41
B. Secure the Vent Sections

B. Secure the Vent Sections

Vertical runs of DVP pipe must be supported every 8 ft. (2.44 m) after the 25 ft. (7.62 m) maximum unsupported rise.

Horizontal sections must be supported every 5 feet (1.52 m).

Vent supports or plumbers strap (spaced 120º apart) may be used to support vent sections. See Figures 10.5 and 10.6.

Wall shield firestops may be used to provide horizontal support to vent sections.

WARNING! Risk of Fire, Explosion or Asphyxiation! Improper support may allow vent to sag and separate. Use vent run supports and connect vent sections per in- stallation instructions. DO NOT allow vent to sag below connection point to appliance.

120º

Figure 10.5 Securing Vertical Pipe Sections

120º

Figure 10.6 Securing Horizontal Pipe Sections

C. Disassemble Vent Sections

Rotate either section (see Figure 10.7) so the seams on both pipe sections are aligned as shown in Figure 10.8.

Pull carefully to separate the pieces of pipe.

Figure 10.7 Rotate Seams for Disassembly

Figure 10.8 Align and Disassemble Vent Sections

Heatilator • HEIR36, HEIR42, HEIR50 • 2285-900 Rev. D • 8/12

41

Page 41
Image 41
Heatiator HEIR50H, HEIR42H, HEIR42T, HEIR50T, HEIR36H, HEIR36T B. Secure the Vent Sections, C. Disassemble Vent Sections