“B” Group: Fine Tuning Functions

Overload Restriction

If the inverter’s output current exceeds a preset current level you specify during acceleration or constant speed, the overload restriction feature automatically reduces the output frequency to restrict the overload. This feature does not generate an alarm or trip event. You can instruct the inverter to apply overload restriction only during constant speed, thus allowing higher currents for acceleration. Or, you may use the same threshold for both acceleration and constant speed.

When the inverter detects an overload, it must decelerate the motor to reduce the current until it is less than the threshold.

You can choose the rate of deceleration that the inverter uses to lower the output current.

Motor

Current

Restriction area

B022

0

t

Output

frequency

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

B023

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring ParametersDrive

 

 

 

“B” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

 

Func.

Name /

Description

Mode

–FEF

–FU

 

Units

 

 

 

 

 

Edit

 

 

 

Code

SRW Display

(EU)

(USA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B021

Overload restriction

Select the operating mode

01

01

 

 

 

 

operation mode

during overload conditions,

 

 

 

 

 

 

 

 

 

 

three options, option codes:

 

 

 

 

 

 

 

 

OL Mode

ON

 

 

 

 

 

 

 

 

00... Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01... Enabled for acceleration

 

 

 

 

 

 

 

 

 

 

and constant speed

 

 

 

 

 

 

 

 

 

 

02... Enabled for constant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

speed only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B022

Overload restriction

Sets the level for overload

Rated current x

 

A

 

 

 

setting

 

restriction, between 20% and

 

1.5

 

 

 

 

 

 

 

150% of the rated current of

 

 

 

 

 

 

 

 

OL LVL

002.40A

 

 

 

 

 

 

 

 

the inverter, setting resolution

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is 1% of rated current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B023

Deceleration rate at

Sets the deceleration rate when

1.0

30.0

 

sec.

 

 

 

overload restriction

inverter detects overload, range

 

 

 

 

 

 

 

 

 

 

is 0.1 to 30.0, resolution is 0.1.

 

 

 

 

 

 

 

 

OL Cnst

0001.0s