3–46

“C” Group: IntelligentTerminal Functions

 

 

 

 

Input Function Summary Table

 

 

 

 

 

 

 

 

 

Option

Terminal

Function Name

 

Description

 

 

Code

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

PIDC

PID Reset

ON

Resets the PID loop controller. The main conse-

 

 

 

 

 

 

quence is that the integrator sum is forced to

 

 

 

 

 

 

zero.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No effect on PID loop controller

 

 

 

 

 

 

 

 

 

27

UP

Remote Control

ON

Accelerates (increases output frequency) motor

 

 

 

 

UP Function (motor-

 

from current frequency

 

 

 

 

ized speed pot.)

 

 

 

 

 

 

OFF

Output to motor operates normally

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

DWN

Remote Control

ON

Decelerates (decreases output frequency) motor

 

 

 

 

DOWN Function

 

from current frequency

 

 

 

 

(motorized speed

 

 

 

 

 

 

OFF

Output to motor operates normally

 

 

 

 

pot.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29

UDC

Remote Control Data

ON

Clears the UP/DWN frequency memory by

 

 

 

 

Clearing

 

forcing it to equal the set frequency parameter

 

 

 

 

 

 

F001. Setting C101 must be set=00 to enable this

 

 

 

 

 

 

function to work.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

UP/DWN frequency memory is not changed

 

 

 

 

 

Configuring ParametersDrive

 

 

 

 

 

 

 

31

OPE

Operator Control

ON

Forces the source of the output frequency setting

 

 

 

 

 

 

 

 

(A001) and the source of the RUN command

 

 

 

 

 

 

(A002) to be from the digital operator

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Source of output frequency set by (A001) and

 

 

 

 

 

 

source of run command set by (A002) is used

 

 

 

 

 

 

 

 

 

50

ADD

ADD frequency

ON

Adds the A145 value (Add Frequency) to the

 

 

 

 

enable

 

output frequency

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Does not add the A145 value to the output

 

 

 

 

 

 

frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51

F-TM

Force Terminal

ON

Force inverter to use input terminals for output

 

 

 

 

Mode

 

frequency and Run command sources

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Source of output frequency set by (A001) and

 

 

 

 

 

 

source of Run command set by (A002) is used

 

 

 

 

 

 

 

 

 

255

Not selected

ON

(input ignored)

 

 

 

 

 

 

 

 

 

 

 

 

OFF

(input ignored)

 

 

 

 

 

 

 

Note 1: When using the Multi-speed Select settings CF1 to CF4, do not display parameter F001 or change the value of F001 while the inverter is in Run Mode (motor running). If it is necessary to check the value of F001 during Run Mode, please monitor D001 instead of F001.