3–37

L200 Inverter

Miscellaneous Settings

The miscellaneous settings include scaling factors, initialization modes, and others. This section covers some of the most important settings you may need to configure.

B032: Reactive current setting – Each L200 inverter model is designed for a particular motor size (hp/power rating). The inverter calculates the motor current while assuming that the motor is matched to the inverter’s size. When using a differently sized motor (or two or more motors in parallel), the inverter must be calibrated for this motor variation. Adjusting parameter B032, Reactive Current Setting, will correct the inverter’s motor current calculation. The inverter uses the current calculation for the following functions:

D002 – Output current monitor

B012 – Level of electronic thermal setting

B212 – Level of electronic thermal setting, 2nd motor

B022 – Overload restriction setting

The current calculation accuracy is normally ±20% under the following conditions:

A single motor with standard frame size and characteristics is connected

The inverter’s output frequency is at 50% or higher of the maximum output frequency

The inverter’s output current is within the rated current

However, it will be necessary to calibrate the current calculation via B032, Reactive Current Setting, if any of these conditions exist:

The motor is smaller than the standard maximum recommended for the inverter

The motor is a two-pole motor type

Two or more motors are connected in parallel to the inverter (be sure to multiply the current by the number of motors when setting B032)

If you do not know the reactive or no-load current for your particular motor, you can calibrate the L200 as follows:

1.Connect the motor directly across the AC line with no load attached to the shaft.

WARNING: Use a disconnect switch or breaker to ensure that you do not connect the motor or inverter to live wiring. Otherwise, there is the danger of electric shock.

2.Run the motor, and measure the no-load current with an AC current clamp, recording the value.

3.Disconnect the motor from the AC line connection, and connect the motor to the L200 inverter output (still with no load attached).

4.Run the motor at the base frequency (value of parameter A003), and monitor the motor current with function D002.

5.If the D002 display value does not match the current clamp value recorded in Step 2, increase or decrease parameter B032 until the best match is achieved.

Parameters Drive

Configuring