3–56

“H” Group: Motor Constants Functions

“H” Group: Motor Constants Functions

The “H” Group parameters configure the inverter for the motor characteristics. You must manually set H003 and H004 values to match the motor. Parameter H006 is factory- set. If you want to reset the parameters to the factory default settings, use the procedure in “Restoring Factory Default Settings” on page 6–8. Use A044 to select the torque control algorithm as shown in the diagram.

Inverter Torque Control Algorithms

 

 

 

A44

 

V/f control,

00

 

 

 

 

 

 

 

 

 

 

constant torque

 

 

 

 

Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V/f control,

01

 

 

 

 

 

 

variable torque

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring

Drive Parameters

 

 

 

 

“H” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

 

Func.

Name /

 

Description

Mode

–FEF

–FU

 

Units

 

Edit

 

Code

SRW Display

 

(EU)

(USA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H003

Motor capacity

 

Nine selections:

Specified by

 

kW

 

 

 

 

0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7

 

the capacity of

 

 

 

AUX K

0.4 kW

 

 

 

 

5.5 / 7.5 / 11

 

each inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

model

 

 

H203

Motor capacity, 2nd

Nine selections:

 

kW

 

 

 

 

setting

 

 

0.2 / 0.4 / 0.75 / 1.5 / 2.2 / 3.7

 

 

 

 

 

 

 

 

 

5.5 / 7.5 / 11

 

 

 

 

 

 

2AUXK

0.4 kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H004

Motor poles setting

 

Four selections:

4

4

 

poles

 

 

 

 

2 / 4 / 6 / 8

 

 

 

 

 

 

AUX P

 

4p

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H204

Motor poles setting, 2nd

Four selections:

4

4

 

poles

 

motor

 

 

2 / 4 / 6 / 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2AUXP

 

4p

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H006

Motor stabilization

 

Motor constant (factory set),

100

100

 

 

constant

 

 

range is 0 to 255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUX KCD

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H206

Motor stabilization

 

Motor constant (factory set),

100

100

 

 

constant, 2nd motor

range is 0 to 255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2AUXKCD

 

100