3–52

“C” Group: IntelligentTerminal Functions

Configuring

Drive Parameters

 

 

Analog Signal Calibration Settings

The functions in the following table configure the signals for the analog output termi- nals. Note that these settings do not change the current/voltage or sink/source character- istics—only the zero and span (scaling) of the signals.

 

 

“C” Function

Run

 

Defaults

 

 

 

 

 

 

 

 

 

Func.

Name /

Description

Mode

–FEF

–FU

 

Units

Edit

 

Code

SRW Display

(EU)

(USA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C081

O input span calibration

Scale factor between the

100.0

100.0

 

%

 

 

 

external frequency command

 

 

 

 

 

 

O-ADJ

0100.0%

 

 

 

 

 

 

on terminals L – O (voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

input) and the frequency

 

 

 

 

 

 

 

 

output, range is 0.0 to 200.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

C082

OI input span calibra-

Scale factor between the

100.0

100.0

 

%

 

tion

 

external frequency command

 

 

 

 

 

 

 

 

on terminals L – OI (current

 

 

 

 

 

 

OI-ADJ

0100.0%

 

 

 

 

 

 

input) and the frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output, range is 0.0 to 200.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

C085

Thermistor input tuning

Range is 0.0 to 200.0%

100.0

100.0

 

%

 

 

 

 

 

 

 

 

 

 

PTC Adj

0100.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C086

[AM] terminal offset

Range is 0.0 to 10.0V

0.0

0.0

 

V

 

tuning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AM-OFFST 0000.0V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 