B–30

ModBus Data Listing

 

 

 

Holding Registers for “A” Group Standard Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Func.

Name

R/W

 

Description

 

Network Data

 

 

 

 

 

 

 

 

 

 

 

Code

 

Reg.

 

Range

 

Res.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A095

Acc1 to Acc2 frequency

R/W

Output frequency at which

007Eh

 

0 to 4000

 

0.1 Hz

 

 

 

transition point

 

Accel1 switches to Accel2,

 

 

 

 

 

 

 

 

 

 

range is 0.0 to 400.0 Hz

 

 

 

 

 

 

 

A295

Acc1 to Acc2 frequency

R/W

007Fh

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transition point, 2nd

 

 

 

 

 

 

 

 

 

 

 

motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A096

Dec1 to Dec2 frequency

R/W

Output frequency at which

0080h

 

0 to 4000

 

0.1 Hz

 

 

 

transition point

 

Decel1 switches to Decel2,

 

 

 

 

 

B

 

 

 

 

range is 0.0 to 400.0 Hz

 

 

 

 

 

 

A296

Dec1 to Dec2 frequency

R/W

0081h

 

 

 

 

 

 

 

 

 

 

 

Appendix

 

 

transition point, 2nd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A097

Acceleration curve

R/W

Set the characteristic curve of

0082h

 

0, 1

 

 

 

 

selection

 

Acc1 and Acc2, two options:

 

 

 

 

 

 

 

 

 

 

00

... linear

 

 

 

 

 

 

 

 

 

 

01

... S-curve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A098

Deceleration curve

R/W

Set the characteristic curve of

0083h

 

0, 1

 

 

 

 

 

selection

 

Acc1 and Acc2, two options:

 

 

 

 

 

 

 

 

 

 

00

... linear

 

 

 

 

 

 

 

 

 

 

01

... S-curve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A101

[OI]–[L] input active

R/W

The output frequency corre-

0084h

 

0 to 4000

 

0.1 Hz

 

 

 

range start frequency

 

sponding to the current input

 

 

 

 

 

 

 

 

 

 

range starting point.

 

 

 

 

 

 

 

 

 

 

Range is 0.00 to 400.0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A102

[OI]–[L] input active

R/W

The output frequency corre-

0085h

 

0 to 4000

 

0.1 Hz

 

 

 

range end frequency

 

sponding to the current input

 

 

 

 

 

 

 

 

 

 

range ending point.

 

 

 

 

 

 

 

 

 

 

Range is 0.00 to 400.0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A103

[OI]–[L] input active

R/W

The starting point for the

0086h

 

0 to 100

 

1 %

 

 

 

range start current

 

current input range.

 

 

 

 

 

 

 

 

 

 

Range is 0. to 100.%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A104

[OI]–[L] input active

R/W

The ending point for the

0087h

 

0 to 100

 

1 %

 

 

 

range end current

 

current input range.

 

 

 

 

 

 

 

 

 

 

Range is 0. to 100.%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A105

[OI]–[L] input start

R/W

Two options:

0088h

 

0, 1

 

 

 

 

frequency enable

 

00

... Use A101 start value

 

 

 

 

 

 

 

 

 

 

01

... Use 0Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A141

A input select for calcu-

R/W

Five options:

00E3h

 

0 to 4

 

 

 

 

late function

 

00

... Digital operator

 

 

 

 

 

 

 

 

 

 

01

... Keypad potentiometer

 

 

 

 

 

 

 

 

 

 

02

... [O] input

 

 

 

 

 

 

 

 

 

 

03

... [OI] input

 

 

 

 

 

 

 

 

 

 

04

... Network variable