B–21

L200 Inverter

ModBus Holding Registers

The following tables list the holding registers for the inverter interface to the network. The table legend is given below.

Function Code - The inverter’s reference code for the parameter or function (same as inverter keypad display)

Name - The standard functional name of the parameter or function for the inverter

R/W - The read-only or read-write access permitted to the data in the inverter

Description - How the parameter or setting works (same as Chapter 3 description).

Reg. - The network register address to the value (some values have a high-byte and low-byte address)

Range - The numerical range for the network value that is sent and/or received

TIP: The network values are binary integers. Since these values cannot have an embedded decimal point, for many parameters it represents the actual value (in engineering units) multiplied by a factor of 10 or 100. Network communications must use the listed range for network data. The inverter automatically divides received values by the appropriate factor in order to establish the decimal point for internal use. Likewise, the network host computer must apply the same factor when it needs to work in engineering units. However, when sending data to the inverter, the network host computer must scale values to the integer range listed for network communications.

Resolution - This is the quantity represented by the LSB of the network value, in engineering units. When the network data range is greater than the inverter’s internal data range, this 1-bit resolution will be fractional.

List of Holding Registers

Func.

Name

R/W

Description

 

Network Data

 

 

 

 

Code

Reg.

 

Range

Res.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output frequency

 

Inverter output frequency (set

001h

 

0 to

0.1 Hz

 

command

 

A001=03 to enable this

 

 

4000

 

 

 

 

network register),

 

 

 

 

 

 

 

range is 0.0 to 400.0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

Inverter status

R/W

00... Initial status

002h

 

0 to 9

 

 

 

01... (Reserved)

 

 

 

 

 

 

 

02... Stop Mode

 

 

 

 

 

 

 

03... Run Mode

 

 

 

 

 

 

 

04... Free-run stop (FRS)

 

 

 

 

 

 

 

05... Jogging

 

 

 

 

 

 

 

06... DC braking

 

 

 

 

 

 

 

07... Retry

 

 

 

 

 

 

 

08... Trip alarm

 

 

 

 

 

 

 

09... Under-voltage

 

 

 

 

 

 

 

 

 

 

 

 

Process Variable (PV)

 

PID loop PV value from the

003h

 

0 to

0.1%

 

 

 

network (set A076=02 to

 

 

1000

 

 

 

 

enable this setting), range is

 

 

 

 

 

 

 

0.0 to 100.0%

 

 

 

 

 

 

 

 

 

 

 

 

B Appendix