3–35

L200 Inverter

Software Lock Mode

The software lock function keeps personnel from accidentally changing parameters in the inverter memory. Use B031 to select from various protection levels.

The table below lists all combinations of B031 option codes and

 

 

 

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

the ON/OFF state of the [SFT] input. Each Check or Ex

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

indicates whether the corresponding parameter(s) can be edited.

 

 

 

 

 

 

 

 

 

Edit

 

 

 

 

 

The Standard Parameters column below shows access is permit-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ted for some lock modes. These refer to the parameter tables

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

throughout this chapter, each of which includes a column titled

 

 

 

 

 

 

 

Run Mode Edit as shown to the right. The marks (Check or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ex ) under the “Run Mode Edit” column title indicate whether access applies to each

 

parameter as defined in the table below. In some lock modes, you can edit only F001 and

 

the Multi-speed parameter group that includes A020, A220, A021–A035, and A038

 

(Jog). However, it does not include A019, Multi-speed operation selection. The editing

 

access to B031 itself is unique, and is specified in the right-most two columns below.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B031

[SFT]

Standard Parameters

F001 and

 

B031

 

 

 

 

Multi-Speed

 

 

 

 

 

Lock

Intelligent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode

Input

Stop

Run

Stop & Run

Stop

 

 

Run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring Parameters Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

00

OFF

Run mode

 

 

 

 

 

 

edit access

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

OFF

Run mode

 

 

 

 

 

 

edit access

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

(ignored)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

(ignored)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Since the software lock function B031 is always accessible, this feature is not the same as password protection used in other industrial control devices.