(2) A setup of output capacity is checked.

(The check method) Please display H003, push FUNC key and check that it is ***.

*Please check having become as shown in H003 of Table 1 and Table 2 about a display of the portion of ***.

(3)Model selection of Sj300/L300P is checked.

(The check method) Please display H-- and check that the displays when pushing FUNC key once are SJ300:H001 and L300P:H003.

Table1. The correspondence table by the setting code model of SJ300

Code

C196

C197

H003

 

(Output

(Voltage

(motor

Model

capacity)

class)

capacity)

-004LF/LFU

0.4

200

0.4

 

 

 

 

-007LF/LFU

0.75

200

0.75

 

 

 

 

-015LF/LFU

1.5

200

1.5

 

 

 

 

-022LF/LFU

2.2

200

2.2

 

 

 

 

-037LF/LFU

3.7

200

3.7

 

 

 

 

-055LF/LFU

5.5

200

5.5

 

 

 

 

-075LF/LFU

7.5

200

7.5

 

 

 

 

-110LF/LFU

11.0

200

11.0

 

 

 

 

-150LF/LFU

15.0

200

15.0

 

 

 

 

-185LF/LFU

18.5

200

18.5

 

 

 

 

-220LF/LFU

22.0

200

22.0

 

 

 

 

-300LF/LFU

30.0

200

30.0

 

 

 

 

-370LF/LFU

37.0

200

37.0

 

 

 

 

-450LF/LFU

45.0

200

45.0

 

 

 

 

-550LF/LFU

55.0

200

55.0

 

 

 

 

Code

C196

C197

H003

 

(Output

(Voltage

(motor

Model

capacity)

class)

capacity)

-007HF/HFE/HFU

0.75

400

0.75

 

 

 

 

-015HF/ HFE/HFU

1.5

400

1.5

 

 

 

 

-022HF HFE/HFU

2.2

400

2.2

 

 

 

 

-037HF/HFU

3.7

400

3.7

 

 

 

 

-040HFE

3.7

400

4.0

 

 

 

 

-055HF/HFE/HFU

5.5

400

5.5

 

 

 

 

-075HF/HFE/HFU

7.5

400

7.5

 

 

 

 

-110HF/HFE/HFU

11.0

400

11.0

 

 

 

 

-150HF/HFE/HFU

15.0

400

15.0

 

 

 

 

-185HF/HFE/HFU

18.5

400

18.5

 

 

 

 

-220HF/HFE/HFU

22.0

400

22.0

 

 

 

 

-300HF/HFE/HFU

30.0

400

30.0

 

 

 

 

-370HF/HFE/HFU

37.0

400

37.0

 

 

 

 

-450HF/HFE/HFU

45.0

400

45.0

 

 

 

 

-550HF/HFE/HFU

55.0

400

55.0

 

 

 

 

Table2. The correspondence table by the setting code model of L300P

Code

C196

C197

H003

 

(Output

(Voltage

(motor

Model

capacity)

class)

capacity)

-110LFR/LFU

11.0

200

11.0

 

 

 

 

-150LFR/LFU

15.0

200

15.0

 

 

 

 

-185LFR/LFU

18.5

200

18.5

 

 

 

 

-220LFR/LFU

22.0

200

22.0

 

 

 

 

-300LFR/LFU

30.0

200

30.0

 

 

 

 

-370LFR/LFU

37.0

200

37.0

 

 

 

 

-450LFR/LFU

45.0

200

45.0

 

 

 

 

-550LFR/LFU

55.0

200

55.0

Code

C196

C197

H003

 

(Output

(Voltage

(motor

Model

capacity)

class)

capacity)

-110HFR/HFE/HFU

11.0

400

11.0

 

 

 

 

-150HFR/HFE/HFU

15.0

400

15.0

 

 

 

 

-185HFR/HFE/HFU

18.5

400

18.5

 

 

 

 

-220HFR/HFE/HFU

22.0

400

22.0

 

 

 

 

-300HFR/HFE/HFU

30.0

400

30.0

 

 

 

 

-370HFR/HFE/HFU

37.0

400

37.0

 

 

 

 

-450HFR/HFE/HFU

45.0

400

45.0

 

 

 

 

-550HFR/HFE/HFU

55.0

400

55.0

 

 

 

 

Table3. Use area code

Local selection

C195

 

 

b085

code

(Use area)

 

(Initial data)

For Japan

JP

 

00

For EU

EU

 

01

For USA

USA

 

02

Table4. Model selection code

 

 

Model selection

C198

 

 

code

(Model selection)

 

 

SJ300

00

 

 

 

L300P

01

 

 

 

3- 4

Page 28
Image 28
Hitachi L300P Series service manual Model selection code C198 Code SJ300 L300P