3.Debug Mode
Additional displays as follows can be seen by turning Debug mode ON (C091
3.1 Monitor mode
No | Functional | Display code | SJ300/L300P A Monitor or data range |
|
|
|
|
1 | Control frequency monitor | d101 | |
2 | d102 | ||
3 | BRD | d103 | |
4 | Electronic thermal monitor | d104 | |
5 | Gate array trip factor monitor | d105 | |
6 | MCU No. monitor | d106 |
d101 ( Output frequency monitor (Hz)): Monitor of the output frequency of the inverter.
d102 ( DC bus voltage monitor (V)): Monitor of the DC bus voltage (VPN) of the inverter.
d103 ( BRD ON monitor (s)): There is an integrated BRD circuit on 11kW and less for SJ300, and 15kW and less for L300P series. You can find accumulated turning ON time for the integrated BRD transistor.
d104 ( Electronic thermal monitor (%)):You can find the usage ratio of electronic thermal performance as %.
d105 (Trip cause monitor of gate array):There are 8 items of trips which are detected by the internal gate array and these items are transmitted to MCU.
Bit7
bit6
Bit5
bit4
bit3
bit2
bit1
bit0
Gate | array IGBT error | IGBT error | Over | Over voltage | Under voltage | IGBT error | Option |
error | W phase | V phase | temperature | (E07) | (E09) | U phase | Ground fault |
(E21) |
|
| (E14) | ||||
(E23) | (E30) | (E30) |
|
| (E30) | ||
|
|
|
|
Contents of d105 are expressed in HEX.
(Example 1) 20
20 (HEX) = 00100000 (BIN)
bit5 = “1”
(Example 1) 62
62 (HEX) = 01100010 (BIN)
bit1, bit5, bit6 = “1 ”
d106(MCU No monitor): Display the software management number of MCU incorporated.