4. The check of control power supply voltage and a control signal

4.1 Control power supply

 

Item

Tolerance level

Measurement place

 

 

 

 

 

 

+

-

 

 

 

 

 

 

PV5

+5V power supply

4.5V - 5.5V

J1 connector 25,16pin

Control terminal

L

 

 

 

 

 

 

PV12 +12V power supply

10.8V

- 13.2V

J1 connector 7pin

Control terminal

L

 

 

 

 

 

 

NV12 -12V power supply

-13.2V

- -10.8V

J1 connector 5pin

Control terminal

L

 

 

 

 

 

 

 

PV24

24V power supply

21.6V

- 26.4V

J1 connector 3,4pin,

Control terminal CM1

Control terminal P24

 

 

 

 

 

 

4.2 Control signal

 

 

 

 

 

 

 

Signal

Measurement place

The contents of operation

Observation waveform

 

 

A main circuit direct-current voltage

 

 

 

VDC

J1 connector 12pin-L

detected signal

 

 

Direct-current voltage

VDC=6.396V/400V*VPN(200Vclass)

 

 

 

 

 

 

 

VDC=6.396V/800V*VPN(400Vclass)

 

 

 

 

 

A motor current detected signal

 

 

3.3V

IUF

J1 connector 9pin-L

 

 

 

At the time of inverter rated load: About

 

 

 

IWF

J1 connector 8pin-L

 

 

0V

3.3 V peak

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-3.3V

 

 

The signal at the time of carrying out a

 

 

 

 

 

trip by the trip factor which a gate array

 

 

 

TRIP

J1 connector 21pin-L

judges (P3-1 reference)

 

Direct-current voltage

 

 

Normal : 5V(H)

 

 

 

 

 

 

 

Inside of a trip : about 0.3V(L)

 

 

 

 

 

 

Phase

failure

protection

detected

 

 

 

PHF

J1 connector 22pin-L

signal

 

 

 

Direct-current voltage

Normal :5V(H)

 

 

 

 

 

 

 

 

 

 

 

Phase failure detection :about0.5V(L)

 

 

 

 

 

The instantaneous power failure signal

 

 

 

IPL

J1 connector 11pin-L

of R0-T0 part

 

 

Direct-current voltage

Power On : about0.5V(L)

 

 

 

 

 

 

 

 

 

Power Off : 5V(H)

 

 

 

 

 

 

Power-module protection

 

 

 

 

GS

J1 connector 20pin-L

Under operation : about 5V(H)

 

Direct-current voltage

 

 

Under a stop

: about 0.5V(L)

 

 

 

US

J1 connector 17pin-L

PWM signal

 

 

5V

 

 

 

 

 

 

 

VS

J1 connector 18pin-L

Upper arm ON

: about 3.5V(L)

3.5V

 

 

WS

J1 connector 19pin-L

lower arm ON

: about 5V(H)

 

0V

Upper arm ON Lower arm ON

 

 

 

 

The trip distinguished by GA is canceled.

5V

 

 

 

 

0.5V

 

 

GS

J1 connector 30pin-L

Normal

: about 5V(H)

 

 

 

 

0V

Reset

Reset

 

 

Under reset : about 0.5V(L)

 

 

 

 

 

 

 

 

4-1