Function Mode

 

Code

Function name

 

 

SJ300 Setting range

Initial data

Note

 

 

 

-FE/-FU/-F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A001

Frequency setting selection

 

01(terminal)/02(operator)/03(RS485)/04(option1)/05(option2)

01/01/02

 

setting

 

A002

Operation setting selection

 

01(terminal)/02(operator)/03(RS485)/04(option1)/05(option2)

01/01/02

 

 

A003

Base frequency

 

 

 

30. - Maximum. frequency(Hz)

50./60./60.

 

 

 

 

 

 

 

Base

 

A203

Base frequency, 2nd motor

 

30. – 2nd M aximum. frequency (Hz)

50./60./60.

 

 

A303

Base frequency, 3rd motor

 

30. - 3rd M aximum. frequency (Hz)

50./60./60.

 

 

 

 

 

 

 

A004

Maximum frequency

 

 

30. – 400. (Hz)

50./60./60.

 

 

 

A204

Maximum frequency, 2nd motor

30. – 400. (Hz)

50./60./60.

 

 

 

A304

Maximum frequency, 3rd motor

30. – 400. (Hz)

50./60./60.

 

 

 

A005

AT terminal selection

 

 

00( Changing of O and OI with AT terminal)/

00

 

setting

 

 

 

01(Changing of O and O2 with AT terminal)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A006

02 selection

 

 

 

00(single)/01(auxiliary speed of O, OI) [no reversible] /

00

 

input

 

 

 

 

0.00-99.99/100.0-400.0 (Hz)

 

 

A011

0 start

 

 

 

 

0.00

 

 

 

 

 

 

 

 

 

02(auxiliary speed of O, OI [reversible]

 

 

Analog

 

 

 

 

 

 

 

 

 

 

 

A012

0 end

 

 

 

 

0.00-99.99/100.0-400.0 (Hz)

0.00

 

 

 

 

 

 

 

 

 

 

A013

0 start rate

 

 

 

0.-100.0 (%)

0.

 

 

 

A014

0 end rate

 

 

 

0.-100.0(%)

100.

 

 

 

A015

0 start selection

 

 

 

00 (external starting frequency)/01(0Hz)

01

 

 

 

A016

O, OI, O2 sampling

 

 

1.-30.(times)

8.

 

 

 

A019

Multi-speed selection

 

 

00(binary : range is to 16 stage speed with 4 terminals)/

00

 

 

 

 

 

01(bit : range is to 8 stage speed with 7 terminals)

 

 

 

 

 

 

 

 

 

 

 

 

 

A020

Multi-speed 0

 

 

 

0.00, starting frequency-maximum. frequency(Hz)

0.00

 

setting

 

A220

Multi-speed 0, 2nd motor

 

 

0.00, starting frequency-2ndmaximum frequency(Hz)

0.00

 

 

A021

Multi-speed1

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A320

Multi-speed 0, 3rd motor

 

 

0.00, starting frequency-3rdmaximum frequency(Hz)

0.00

 

frequency

 

 

 

 

 

 

 

 

 

 

 

A022

Multi-speed2

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

 

 

 

 

 

 

A023

Multi-speed3

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A024

Multi-speed4

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

speed,jogging

 

A025

Multi-speed5

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

 

 

 

 

 

 

A026

Multi-speed6

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A027

Multi-speed7

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A028

Multi-speed8

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

Multistage

 

A029

Multi-speed9

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

A030

Multi-speed10

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

 

 

 

 

 

 

A031

Multi-speed11

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A032

Multi-speed12

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A033

Multi-speed13

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A034

Multi-speed14

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A035

Multi-speed15

 

 

 

0.00, starting frequency-maximum frequency(Hz)

0.00

 

 

 

A038

Jogging frequency

 

 

0.00, starting frequency-9.99(Hz)

1.00

 

 

 

 

 

 

 

 

 

00(free-run on JG stop / invalid on running) / 01(stop decelerating on

 

 

 

 

 

 

 

 

 

 

JG stop / invalid on running) / 02(DC braking on JG stop/invalid on

 

 

 

 

A039

Jogging selection

 

 

running) / 03(free-run on JG stop/valid on running[JG after stop

00

 

 

 

 

 

 

 

 

 

decelerating]) / 04 (stop decelerating on JG stop/valid on running) / 05

 

 

 

 

 

 

 

 

 

 

(DC braking on JG stop/valid on operating)

 

 

 

 

A041

Torque boost selection

 

 

00 (manual torque boost) / 01 (automatic torque boost)

00

 

 

 

A241

Torque

boost

selection,

2nd

00 (manual torque boost) / 01 (automatic torque boost)

00

 

characteristic

 

motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A042

Manual torque boost

 

 

0.0-20.0(%)

1.0

 

 

 

 

 

 

 

 

A242

Manual torque boost, 2nd motor

0.0-20.0(%)

1.0

 

 

 

A342

Manual torque boost, 3rd motor

0.0-20.0(%)

1.0

 

V/f

 

A043

Manual torque boost point

 

0.0-50.0(%)

5.0

 

 

 

Manual

torque

boost

point,

nd

 

 

 

 

 

A243

2

0.0-50.0(%)

5.0

 

 

 

motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual

torque

boost

point,

rd

 

 

 

 

 

A343

3

0.0-50.0(%)

5.0

 

 

 

motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A044

1s t control

 

 

 

00/(VC)/01(VP1.7power)/02(free V/f setting)/03(SLV)/

00

 

 

 

 

 

 

04(0Hz-SLV)/05(V2)

 

 

 

 

 

 

 

 

 

 

 

 

 

A244

2nd control

 

 

 

00/(VC)/01(VP1.7power)/02(free V/f setting) /03(SLV)/04(0Hz-SLV)

00

 

 

 

A344

3rd control

 

 

 

00/(VC)/01(VP1.7power)

00

 

 

 

A045

Output voltage gain

 

 

20. - 100.

100.

 

braking

 

A051

DC braking selection

 

 

00(invalid)/01(valid)

00

 

 

 

 

 

 

 

 

A052

DC braking frequency

 

 

0.00-60.00(Hz)

0.50

 

current

 

A053

DC braking wait time

 

 

0.0 - 5.0(s)

0.0

 

 

A054

DC braking power

 

 

0. - 100. ( %) <0.-80.(%)>

0.

 

 

 

 

 

 

Direct

 

A055

DC braking time

 

 

 

0.0 - 60.0(s)

0.0

 

 

A056

DC braking edge/level selection

00(edge action)/01(level action)

01

 

 

 

 

 

 

A057

DC braking power (starting time)

0. - 100. ( %) <0.-80.(%)>

0.

 

 

 

A058

DC braking time(starting time)

 

0.00-60.0(s)

0.0

 

 

 

A059

DC carrier frequency

 

 

0.5-15(kHz) Derating <0.5-10kHz>

5.0<3.0>

 

(Note) < > indicate the setting range of 75 to 150kW

1- 3

Page 6
Image 6
Hitachi L300P Series service manual Function Mode