Function Mode

 

 

Code

limiter,jump

 

A061

 

 

A063

 

 

A261

 

 

A062

lower

 

A262

 

A064

 

 

 

 

A065

andUpper

frequency

A066

A067

 

 

 

 

A068

 

 

A069

 

 

A070

 

 

A071

 

control

A072

 

A073

 

 

 

PID

A074

 

A075

 

 

 

 

A076

 

AVR

A081

 

A082

 

 

 

 

 

Function name

SJ300 Setting range

Initial data

Note

-FE/-FU/-F

 

 

 

 

1s t frequency maximum limiter

0.00, 1s t frequency lower limitter - maximum frequency(Hz)

0.00

 

2nd frequency maximum limiter

0.00, 2nd frequency lower limiter-2ndsetting maximum frequency(Hz)

0.00

 

1s t frequency minimum limiter

0.00, start frequency-maximum frequency(Hz)

0.00

 

2nd frequency minimum limiter

0.00, start frequency-2nd

setting maximum frequency(Hz)

0.00

 

Jump frequency1

0.00-99.99/100.0-400.0(Hz)

0.00

 

Jump frequency Width 1

0.00-10.00(Hz)

0.50

 

Jump frequency2

0.00-99.99/100.0-400.0(Hz)

0.00

 

Jump frequency Width 2

0.00-10.00(Hz)

0.50

 

Jump frequency3

0.00-99.99/100.0-400.0(Hz)

0.00

 

Jump frequency Width 3

0.00-10.00(Hz)

0.50

 

Acceleration stop frequency

0.00-99.99/100.0-400.0(Hz)

0.00

 

Acceleration stop time

0.00-60.0(s)

0.0

 

PID selection

00(invalid)/01(valid)

00

 

PID-P gain

0.2-5.0

1.0

 

PID-I gain

0.0-3600.(s)

1.0

 

PID-D gain

0.00-100.0(s)

0.00

 

PID scale

0.01-99.99(%)

1.00

 

PID feedback selection

00(feedback : OI)/01(feedback : O)

00

 

AVR selection

00(ON always)/01(OFF always)/02(OFF on decelerating)

00/00/02

 

 

 

 

(230/400)/

 

Motor voltage selection

200/215/220/230/240,

380/400/415/440/460/480

(230/460)/

 

 

 

 

(200/400)

 

 

 

A085

Operation mode selection

00(normal operation)/01(energy-saving operation)/02(Fuzzy)

00

 

 

 

A086

Energy-saving response-

0.0-100.0

50.0

 

 

 

accuracy adjustment

 

 

 

function

 

 

 

 

 

 

A092

Acceleration time2

 

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

 

 

A292

Acceleration time2(2nd

motor)

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

 

 

A392

Acceleration time2(3rd

motor)

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

 

 

adjustable

A093

Deceleration time2

 

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

 

 

A293

Deceleration time2(2nd motor)

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

 

 

A393

Deceleration time2(3rd

motor)

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

 

 

A094

2nd stage adjustable selection

00(change with 2CH terminal)/01(change with setting)

00

 

 

mode/

A294

2nd stage adjustable

 

00(change with 2CH terminal)/01(change with setting)

00

 

 

selection(2nd motor)

 

 

 

 

 

 

 

 

 

 

nd

 

 

 

 

 

A095

2 acceleration frequency

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

Operation

 

 

A295

2nd acceleration

 

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

frequency(2nd motor)

 

 

 

 

 

 

 

 

 

A096

2nd deceleration frequency

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

A296

2nd deceleration frequency

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

(2nd motor)

 

 

 

 

 

 

 

 

 

 

 

A097

Acceleration pattern selection

00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve)

00

 

 

 

A098

Deceleration pattern selection

00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve)

00

 

 

 

A101

OI start

 

0.00-99.99/100.0-400.0(Hz)

0.00

 

External frequency

 

A102

OI end

 

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

A103

OI start rate

 

0.-100. (%)

20.

 

 

A104

OI end rate

 

0.-100. (%)

100.

 

adjustment

A105

OI start selection

 

00(external start frequency)/01(0Hz)

01

 

A111

O2 start

 

-400.--100./-99.9-0.00-99.9/100.-400.(Hz)

0.00

 

A112

O2 end

 

-400.--100./-99.9-0.00-99.9/100.-400.(Hz)

0.00

 

A113

O2 start rate

 

-100. - 100. (%)

-100.

 

A114

O2 end rate

 

-100. - 100. (%)

100.

 

 

 

 

 

Accel,

 

A131

Acceleration curve constant

01(small swelling)-10(large swelling)

02

 

Decel

A132

Deceleration curve constant

01(small swelling-10(large swelling)

02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b001

Retry selection

 

00(trip)/01(0Hz start)/02(start after equal frequency)/

00

 

failure

 

 

03(trip after equaling frequency and deceleration stop)

 

 

 

 

 

 

 

 

b002

Allowable under-voltage power

0.3-1.0(s)

1.0

 

 

failure time

 

 

 

 

 

 

 

 

power

 

 

 

 

 

 

 

b003

Retry wait time

 

0.3-100.(s)

1.0

 

 

b004

Instantaneous power failure/

00(invalid/01(valid)/02(invalid during stop and deceleration by stop

00

 

Instantaneous

 

under-voltage trip during stop

command)

 

 

 

 

 

 

b005

Instantaneous power failure/

00(16 times)/01(free)

00

 

 

under-voltage retry time

 

restart

 

selection

 

 

 

 

b006

Open-phase selection

 

00(invalid)/01(valid)

00

 

b007

Frequency setting to match

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

 

1- 4

Page 7
Image 7
Hitachi L300P Series service manual Code