Function Mode

 

 

Code

 

Function name

L300P Setting range

Initial data

N o t e

 

 

 

-FE/-FU/-FR

 

 

 

 

 

 

 

/ jump

 

A061

1s t

frequency upper limiter

0.00, 1s t frequency lower limiter-maximum frequency(Hz)

0.00

 

 

A261

2nd

frequency upper limiter

0.00, 2 nd frequency lower limiter-2ndsetting maximum

0.00

 

 

 

 

 

frequency(Hz)

 

 

 

 

 

 

 

limiter

 

A062

1s t

frequency lower limiter

0.00, start frequency-maximum frequency(Hz)

0.00

 

 

A262

2nd

frequency lower limiter

0.00, start frequency-2ndsetting maximum frequency(Hz)

0.00

 

 

 

 

lower

 

A063

Jump frequency1

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

A065

Jump frequency2

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

A064

Jump frequency Width 1

0.00-10.00(Hz)

0.50

 

 

 

 

 

 

 

 

andUpper

frequency

A066

Jump frequency Width 2

0.00-10.00(Hz)

0.50

 

A067

Jump frequency3

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

 

 

 

A068

Jump frequency Width 3

0.00-10.00(Hz)

0.50

 

 

 

A069

Acceleration stop frequency

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

A070

Acceleration stop time

0.00-60.0(s)

0.0

 

 

control

A071

PID selection

00(invalid)/01(valid)

00

 

 

A072

PID-P gain

0.2-5.0

1.0

 

 

 

A073

PID-I gain

0.0-3600.(s)

1.0

 

 

PID

A074

PID-D gain

0.00-100.0(s)

0.00

 

 

A075

PID scale

0.01-99.99

1.00

 

 

 

 

 

 

A076

PID feedback selection

00(feedback : OI)/01(feedback : O)

00

 

 

 

A081

AVR selection

00(ON always)/01(OFF always)/02(OFF on decelerating)

00/00/02

 

 

AVR

 

 

 

 

(230/400)

 

 

A082

Motor voltage selection

200/215/220/230/240, 380/400/415/440/460/480

(230/460)

 

 

 

 

 

 

 

(200/400)

 

 

 

A085

Operation mode selection

00(normal operation)/01(energy-saving operation)

00

 

 

function

A292

Energy-saving response-

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

 

 

2nd

acceleration time2

 

 

 

A086

accuracy adjustment

0.0-100.0

50.0

 

 

 

A092

Acceleration time2

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

 

 

adjustable

 

 

 

 

 

 

 

A294

2nd

stage adjustable

00(change with 2CH terminal)/01(change with setting)

00

 

 

 

A093

Deceleration time2

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

 

 

 

A293

2nd

deceleration time2

0.01-99.99/100.0-999.9/1000.-3600.(s)

15.00

 

 

 

A094

2nd stage adjustable selection

00(change with 2CH terminal)/01(change with setting)

00

 

 

mode/

 

selection(2nd motor)

 

 

 

 

A095

2nd

acceleration

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

2nd

acceleration frequency

 

 

Operation

A295

frequency(2nd motor)

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

 

 

 

 

A096

2nd

deceleration frequency

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

 

 

 

A296

2nd

deceleration frequency

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

(2nd motor)

 

 

 

 

 

 

 

 

 

A097

Acceleration pattern selection

00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve)

00

 

 

 

A098

Deceleration pattern selection

00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve)

00

 

frequencyExternal

 

A101

OI start

0.00-99.99/100.0-400.0(Hz)

0.00

 

adjustment

A102

OI end

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

 

 

 

A103

OI start rate

0.-100. ( %)

20.

 

 

 

A104

OI end rate

0.-100. ( %)

100.

 

 

 

A105

OI start selection

00(external start frequency)/01(0Hz)

01

 

 

 

A111

O2 start

-400.--100./-99.9-0.00-99.9/100.-400.(Hz)

0.00

 

 

 

A112

O2 end

-400.--100./-99.9-0.00-99.9/100.-400.(Hz)

0.00

 

 

 

A113

O2 start rate

-100. - 100. (%)

-100.

 

 

 

A114

O2 end rate

-100. - 100. (%)

100.

 

Accel

Decel

A131

Acceleration curve constant

01(small swelling)-10(large swelling)

02

 

A132

Deceleration curve constant

01(small swelling-10(large swelling)

02

 

 

 

b001

Retry selection

00(trip)/01(0Hz start)/02(start after equal frequency)/

00

 

failure

 

03(trip after equaling frequency and deceleration stop)

 

 

 

 

 

 

 

 

b002

Allowable under-voltage

0.3-1.0(s)

1.0

 

 

 

 

 

 

power failure time

 

power

 

 

 

 

 

 

b003

Retry wait time

0.3-100.(s)

1.0

 

 

 

 

 

 

 

Instantaneous power-

00(invalid/01(valid)/

 

 

Instantaneous

 

b004

failure/under-voltage trip

00

 

restart

00(invalid)/01(valid)

 

b006

Open-phase selection

00

 

 

 

 

during stop

02(invalid during stop and deceleration by stop command)

 

 

 

 

 

Instantaneous power-

 

 

 

 

 

b005

failure/under-voltage

00(16 times)/01(free)

00

 

 

 

 

retry time selection

 

 

 

 

 

 

 

 

 

 

 

 

b007

Frequency setting to match

0.00-99.99/100.0-400.0(Hz)

0.00

 

 

 

b012

Electronic thermal level

0.2*constant current-1.20*constant current(A)

Rated

 

 

 

Current of

 

 

 

 

 

 

 

inverter

 

 

 

 

Electronic thermal level

 

Rated

 

 

 

b212

0.2*constant current-1.20*constant current(A)

Current of

 

 

 

(2nd motor)

 

 

 

 

 

 

 

inverter

 

Electronic thermal

b013

Electronic thermal

00/(reduced characteristic)01(constant torque characteristic)/

01/01/00

 

characteristic selection

02(free setting)

 

 

 

 

 

Electronic thermal

00/(reduced characteristic)01(constant torque characteristic)/

 

 

b213

characteristic selection

01/01/00

 

02(free setting)

 

 

(2nd motor)

 

 

 

 

 

 

b015

Free electronic thermal

0.-400.(Hz)

0.

 

frequency 1

 

 

 

 

 

b016

Free electronic thermal

0.0-1000.(A)

0.0

 

current 1

 

 

 

 

 

b017

Free electronic thermal

0.-400.(Hz)

0.

 

frequency 2

 

 

 

 

 

b018

Free electronic thermal

0.0-1000. (A)

0.0

 

current 2

 

 

 

 

 

b019

Free electronic thermal

0.-400.(Hz)

0.

 

frequency 3

 

 

 

 

 

b020

Free electronic thermal

0.0-1000.(A)

0.0

 

current 3

 

 

 

 

 

1- 12

Page 15
Image 15
Hitachi L300P Series service manual Pid