5.6 Parts replacement

Inverter is consists from many electrical components. And inverter cannot work properly unless all of them works normal. Electrical components in following table are the components which may degrade according to the usage period.

HITACHI recommend to replace those electrical components periodically to avoid any expected failure caused by them.

Parts name

Recommended

Remarks

 

period for

 

 

replacement

 

Cooling fan

2 ~ 3 years

Replace with fresh one.

DC bus capacitors

5 years

Replace with fresh one. (Decide after inspection.)

Electrolytic capacitors

5 years

Replace with fresh one. (Decide after inspection.)

on PCB

 

 

Relays

-

Inspection in advance

(1) Cooling fan

Lifetime of the cooling fan depends on the usage condition, however it is normally around 35,000 hours. That means it is recommended to replace the cooling fan every 2 ~ 3 years in case the inverter operates continuously. Of course it should be replaced immediately in case the abnormality is found.

(How to remove cooling fan for mold case)

Remove terminal cover and front cover.

Reconfirm that the charge lamp is turned OFF.

ƒPush both side of the cooling fan holder plate and pull out like following figure. „ Remove the connector for fan connection.

ƒ

(How to fix cooling fan for mold case)

Pay attention to the direction of the cooling fan.

Connect the fan connector to J21 or J22 (depends on the model) on the power PCB.

ƒFix the cooling fan holder board to the inverter main body.

Fix the front cover and terminal cover.

Label side of

cooling fan

5- 5

Page 34
Image 34
Hitachi L300P Series service manual Parts replacement