Function Mode
| Code | Function name | L300P Setting range | Initial data | N o t e | |
|
| |||||
|
|
|
|
|
| |
|
| A001 | Frequency setting selection | 00(VR)/01(terminal)/02(operator)/03(RS485)/ | 01/01/00 |
|
|
| 04(option1)/05(option2) |
| |||
|
|
|
|
|
| |
setting |
| A002 | Operation setting selection | 01(terminal)/02(operator)/03(RS485)/04(option1)/05(option2) | 01/01/02 |
|
| A003 | Base frequency | 30. - Maximum. frequency(Hz) | 50./60./60. |
| |
|
|
| ||||
Base |
| A203 | Base frequency, 2nd motor | 30. - 2nd M aximum. frequency (Hz) | 50./60./60. |
|
| A004 | Maximum frequency | 30. - 400. (Hz) | 50./60./60. |
| |
|
|
| ||||
|
| A204 | Maximum frequency, 2nd | 30. - 400. (Hz) | 50./60./60. |
|
|
| motor |
| |||
|
|
|
|
|
| |
|
| A005 | AT terminal selection | 00( Changing of O and OI with AT terminal)/01(Changing of O and O2 | 00 |
|
|
| with AT terminal) |
| |||
setting |
|
|
|
|
| |
|
|
| /02(auxiliary speed of O, OI [reversible] |
|
| |
|
| A006 | 02 selection | 00(single)/01(auxiliary speed of O, OI) [no reversible] | 00 |
|
|
|
|
| |||
input |
|
|
|
|
|
|
| A011 | 0 start | 0.00 |
| ||
|
|
| ||||
Analog |
| A012 | 0 end | 0.00 |
| |
| A013 | 0 start rate | 0. |
| ||
|
|
| ||||
|
| A014 | 0 end rate | 100. |
| |
|
| A015 | 0 start selection | 00 (external starting frequency)/01( OHz) | 01 |
|
|
| A016 | O, OI, O2 sampling | 8. |
| |
|
| A019 | 00(binary : range is to 16 stage speed with 4 terminals)/01(bit : range | 00 |
| |
|
| is to 6 stage speed with 5 terminals) |
| |||
|
|
|
|
|
| |
|
| A020 | 0.00, starting | 0.00 |
| |
|
| A220 | 0.00, starting | 0.00 |
| |
|
| A021 | 0.00, starting | 0.00 |
| |
setting |
| A022 | 0.00, starting | 0.00 |
| |
| A024 | 0.00, starting | 0.00 |
| ||
|
| A023 | 0.00, starting | 0.00 |
| |
frequency |
|
|
|
|
|
|
| A025 | 0.00, starting | 0.00 |
| ||
|
| A026 | 0.00, starting | 0.00 |
| |
|
| A027 | 0.00, starting | 0.00 |
| |
speed,jogging |
| A028 | 0.00, starting | 0.00 |
| |
| A032 | 0.00, starting | 0.00 |
| ||
|
| A029 | 0.00, starting | 0.00 |
| |
|
| A030 | 0.00, starting | 0.00 |
| |
|
| A031 | 0.00, starting | 0.00 |
| |
Multistage |
|
|
|
|
|
|
| A033 | 0.00, starting | 0.00 |
| ||
|
|
| ||||
|
| A034 | 0.00, starting | 0.00 |
| |
|
| A035 | 0.00, starting | 0.00 |
| |
|
| A038 | Jogging frequency | 0.00, starting | 1.00 |
|
|
|
|
|
|
| |
|
|
|
| JG stop / invalid on running) / 02(DC braking on JG stop/invalid on |
|
|
|
| A039 | Jogging selection | running) / | 00 |
|
|
|
|
| decelerating]) / 04 (stop decelerating on JG stop/valid on running) / |
|
|
|
|
|
| 05 (DC braking on JG stop/valid on operating) |
|
|
|
| A041 | Torque boost selection | 00 (manual torque boost) / 01 (automatic torque boost) | 00 |
|
|
| A241 | Torque boost selection, 2nd | 00 (manual torque boost) / 01 (automatic torque boost) | 00 |
|
|
| motor |
| |||
characteristic |
|
|
|
|
| |
| A042 | Manual torque boost point, 2nd | 1.0 |
| ||
|
| Manual torque boost |
| |||
|
| A242 | Manual torque boost, 2nd motor | 1.0 |
| |
|
| A043 | Manual torque boost point | 5.0 |
| |
V/f |
| A243 | motor | 5.0 |
| |
|
|
|
|
| ||
|
| A044 | 1s t control | 00/(VC)/01(VP1.7power)/02(free V/f setting) | 00 |
|
|
| A244 | 2nd control | 00/(VC)/01(VP1.7power)/02(free V/f setting) | 00 |
|
|
| A045 | Output voltage gain | 20. - 100. (%) | 100. |
|
|
| A051 | DC braking selection | 00(invalid)/01(valid) | 00 |
|
|
| A052 | DC braking frequency | 0.50 |
| |
braking |
| A053 | DC braking wait time | 0.0 - 5.0(s) | 0.0 |
|
|
| A054 | DC braking power | 0. - 70. (%) | 0. |
|
current |
| A055 | DC braking time | 0.0 - 60.0(s) | 0.0 |
|
| A056 | DC braking edge/level | 00(edge action)/01(level action) | 01 |
| |
|
|
| ||||
|
| selection |
| |||
|
|
|
|
|
| |
Direct |
| A057 | DC braking power | 0. - 70. (%) | 0. |
|
| (starting time) |
| ||||
|
|
| ||||
|
|
|
|
|
| |
|
| A058 | DC braking time | 0.0 |
| |
|
| (starting time) |
| |||
|
|
|
|
|
| |
|
| A059 | DC carrier frequency | 3.0 |
|
(Note) < > indicate the setting range of 90 to 132kW
1- 11