Flanged Globe Valve

VGF2

VGF Flanged Globe Valves are used for 2-position or modulating control of steam, hot water, or chilled water-glycol solutions up to 50 percent concentration in heating, ventilation and air conditioning (HVAC) systems. They can be operated by ML6984/7984, ML6420/6425, ML6421/7421 Electric Linear Actuators, MP953 Pneumatic Actuators, Modutrol™ Motors with Q5001 valve linkage, or

MN/MS Series Direct Coupled

Actuators with Q5020 valve

linkage.

 

 

SPECIFICATIONS

 

Valve Type

Globe Valve

Body Pattern

Two-way

Flow characteristic

Equal percentage or Linear

Connection Type

Flanged

Valve Action

Step down to close

Controlled Medium

Hot/Chilled Water with up to

 

50% Glycol; Steam

Leakage Rating

0.05% of Cv

Maximum Safe Operating Pressure

400 psig (2750 kPa)

Maximum Differential Pressure Ratings

 

(Close-off)

Varies with actuator force

Fluid Temperature Range

20 F to 250 F, steam 335 F

 

(-7 C to 120 C, steam 180 C)

Actuation

Must be purchased separately

Stem Travel

 

2-1/2 and 3 in. valves

3/4 in. (20 mm)

4 to 6 in. valves

1-1/2 in. (39 mm)

Bonnet Size

 

2-1/2 and 3 in. valves

1-3/8 in. (35 mm)

4 to 6 in. valves

1-7/8 in. (47.6 mm)

Materials

 

(Body)

Cast Iron ASTM A126 Class B

(Stem)

Stainless Steel

(Seat)

Stainless Steel

(Cartridge)

Stainless Steel

(Plug/Ball/Disc)

Stainless Steel

(Packing)

Spring-loaded PTFE cone

 

rings

 

 

FEATURES

ANSI Class 125 and Class 250 cast iron bodies with flanged end connections.

Equal percentage and linear flow characteristics

Face-to-face flange dimensions per ANSI/ISA S75.03 standard.

Sizes from 2-1/2 to 6 in.

Stainless steel trim standard for long life span.

ANSI CLass III seat leakage

Steam inlet pressure up to 125 psig and 353 F maximum temperature.

Self-adjusting packing.

Accurate positioning with equal percentage and linear flow characteristics to ensure precise temperature control.

Universal bonnet for direct-coupled electric and pneumatic actuators for easy mounting, or linkage coupled Modutrol™ Motors and MN/MS Series direct coupled actuators.

Not suitable for combustible gasses.

DIMENSIONS DIAGRAM

STROKE Y

D

B

C

A

1 DOTTED LINE REPRESENTS ANSI 125 VALVE BONNET.

MODEL

 

DIMENSIONS, IN. (MM)

 

 

 

 

 

 

 

NUMBER

A

B

C

E

Y

 

 

 

 

 

 

2-WAY VALVES, ANSI CLASS 125. STEM DOWN TO CLOSE. EQUAL

PERCENTAGE OR LINEAR FLOW CHARACTERISTIC

 

 

 

 

 

 

 

 

VGF21_S25

10-7/8 (276)

4-3/8 (112)

7 (178)

3-1/2 (89)

13/16 (20)

 

 

 

 

 

 

VGF21_S30

11-3/4 (298)

6-3/8 (161)

7-1/2 (191)

 

 

VGF21_S40

13-7/8 (352)

5-7/8 (150)

9 (229)

5-1/4 (133)

1-1/2 (38)

 

 

 

 

 

 

VGF21_S50

15-3/4 (400)

6-3/16 (157)

10 (254)

 

 

VGF21_S60

17-3/4 (451)

6-3/16 (157)

11 (279)

 

 

 

 

 

 

 

 

2-WAY VALVES, ANSI CLASS 250. STEM DOWN TO CLOSE. EQUAL

PERCENTAGE FLOW CHARACTERISTIC

 

 

 

 

 

 

 

 

 

VGF22ES25

11-1/2 (292)

4-3/8 (112)

7-1/2 (191)

3-1/2 (89)

13/16 (20)

VGF22ES30

12-1/2 (318)

6-3/8 (161)

8-1/4 (210)

 

 

 

 

 

 

 

 

VGF22ES40

14-1/2 (368)

5-7/8 (150)

10 (254)

5-1/4 (133)

1-1/2 (38)

VGF22ES50

16-5/8 (422)

6-3/16 (157)

11 (279)

 

 

 

 

 

 

 

 

VGF22ES60

18-5/8 (473)

6-3/16 (157)

12-1/2 (318)

 

 

 

 

 

 

 

 

2-WAY VALVES, PRESSURE-BALANCED, ANSI CLASS 125. STEM DOWN TO

CLOSE. EQUAL PERCENTAGE OR LINEAR FLOW CHARACTERISTIC

 

 

 

 

 

 

VGF21_P25

10-7/8 (276)

4-3/16 (107)

7 (178)

3-1/2 (89)

13/16 (20)

 

 

 

 

 

 

VGF21_P30

11-3/4 (298)

5-7/8 (150)

7-1/2 (191)

 

 

 

 

 

 

 

 

VGF21_P40

13-7/8 (352)

5-7/8 (150)

9 (229)

5-1/4 (133)

1-1/2 (38)

 

 

 

 

 

 

VGF21_P50

15-3/4 (400)

6-1/8 (156)

10 (254)

 

 

 

 

 

 

 

 

VGF21_P60

17-3/4 (451)

6-1/8 (156)

11 (279)

 

 

 

 

 

 

 