Non-Spring Return Direct Coupled Actuator

ML6161; ML7161

Used to control dampers in applications such as variable air volume (VAV) terminal units and for mounting on ball valves; suitable for use with SPDT or floating thermostats or building automation controls.

FEATURES

Control for air damper applications with up to 10 sq.ft. assuming 3.5 lb-in. per sq.ft. of damper area, velocity independent.

Superior A/C synchronous sub-motor for consistent timing and actuator longevity.

Eliminate need for limit switches or mechanical stops by providing magnetic coupling.

All models include manual declutch lever, and bag assembly with two minimum position setscrews.

Mount directly on 3/8 in. or 1/2 in. square or round damper shaft.

Selectable 45, 60, and 90 degree stroke in either clockwise or counterclockwise direction.

SPECIFICATIONS

 

Actuator Type

Damper

Rotational Stroke

90 degrees

Fail Safe Mode

Non-Spring Return

Rated Torque

35 lb-in. (4 Nm)

External Auxiliary Switches Available ..

Yes, 201052B

Electrical Connections

Screw terminals

Environmental Rating

NEMA1

Feedback

With accessory

Frequency

50 Hz, 60 Hz

Manual operation

Declutch mechanism

Mounting

Direct Coupled

Maximum Noise Rating,

 

Driving (dBA @ 1m)

45

Timing, Nominal Driving at 60 Hz

90 sec., 180 sec. or 420 sec.

Power Consumption, Driving

1.8 VA or 5.4 VA

Rotation to Open

By wiring

Rotational Stroke Adjustment

Mechanically limited at 45 or

 

60 degrees in cw or ccw

 

directions

Compatible Damper Shafts

3/8 to 1/2 in. square or round

 

(10 to 13 square/round)

Shaft Adapter Type

Aluminum Hub, two set screws

Supply Voltage

24 Vac ±20%

Materials

Steel plate and Plenum rated

 

plastic

Operating Humidity Range (% RH)

5 to 95% RH, non-condensing

Ambient Temperature Range

20 F to 125 F (-18 C to 50 C)

Storage Temperature Range

20 F to 130 F (-18 C to 54 C)

Weight

1.5 lb (0.68 kg)

Includes

4074ENY Bag Assembly

APPROVALS

 

CE

89/336/ECC, 73/23/EEC

C-Tick

N314

Underwriters Laboratories, Inc

UL873, Plenum Rated

Canadian Underwriters

 

Laboratories, Inc

cUL C22.2 No. 24-93

 

 

DIMENSIONS DIAGRAMS

 

 

2-7/8

(73)

 

 

 

1-11/16

 

 

 

(42)

 

1 (25)

OPTIONAL

1/8

 

 

(3)

 

 

AUXILIARY

 

 

SWITCH

 

CW

4-7/8

 

 

(123)

 

 

 

 

 

COM

4-1/4

 

 

 

 

 

CCW

(108)

 

 

 

 

 

 

11/16

 

 

 

(18)

 

7/8

 

 

 

(22)

3-3/8 (86)

 

1-5/16

 

 

(33)

 

 

 

 

 

2-1/2 (64)

 

 

 

M18016

 

 

 

 

1

 

 

 

(25)

 

 

 

5-9/16

 

 

 

(141)

 

 

24 Vac

4-7/8

 

 

(123)

 

 

T1

4-1/4

 

 

T2

(108)

 

 

-

 

 

 

+

 

 

 

+

 

 

 

2-10 Vdc

 

 

 

4-20 mA

 

 

15/32 (12)

11/16

 

(18)

 

1/8

 

 

 

 

 

(3)

5/16 (8)

 

 

 

 

 

 

1-11/16

 

 

 

(43)

 

 

 

3-3/8 (86)

 

 

1-13/16 (46)

 

3-5/8 (92)

3 IN. (76 MM)

 

 

 

MINIMUM SPACING

 

 

 

REQUIRED

 

 

 

FOR REMOVING

 

 

 

CONDUIT COVER

 

 

 

7/8 (22)

3-3/4 (95)

2-7/8 (73) 1-11/16

(42)

OPTIONAL

 

AUXILIARY

1/8

SWITCH

 

(3)

1/8

(3)

1-5/16

(33)

3 (76)

M22990

1

(25)

1-13/16

(46)

5-7/8

(149)

M18018

88

Page 88
Image 88
Honeywell MS4103 manual Non-Spring Return Direct Coupled Actuator, ML6161 ML7161