Spring Return Direct Coupled Actuator

S05 Series (MS4105; MS7105; MS7405; MS7505; MS8105)

MS4105, MS7405, MS7505, MS8105 Spring Return Direct Coupled Actuators (DCA) are used within heating, ventilating, and air- conditioning (HVAC) systems. They can drive a variety of quarter-turn, final control elements requiring spring return fail-safe operation.

FEATURES

Volume control dampers, mounted directly to the drive shaft or remotely (with the use of accessory hardware).

Quarter-turn rotary valves, such as ball or butterfly valves mounted directly to the drive shaft.

Linear stroke globe or cage valves mounted with linkages to provide linear actuation.

SPECIFICATIONS

 

Actuator Type

Damper, Valve

Rotational Stroke

95 ±3 degrees

Fail Safe Mode

Spring Return

Rated Torque

44 lb-in. (5 Nm)

External Auxiliary Switches Available ..

No

Electrical Connections

Enclosed screw terminal strip

 

(22 to 14 AWG)

Environmental Rating

NEMA2

Frequency

50 Hz, 60 Hz

Mounting

Direct Coupled

Maximum Noise Rating, Holding (dBA @ 1m) 20 (no audible noise) Maximum Noise Rating, Driving (dBA @ 1m) 50

Timing, Nominal Driving at 60 Hz

45 sec. or 90 sec.

Power Consumption, Driving

7.5 VA, 8 VA, or 11 VA

Rotation to Open

By switch

Rotational Stroke Adjustment

Mechanically limited 5 degree

 

increments

Compatible Damper Shafts

3/8 to 5/8 round or 1/4 to 1/2

 

square

 

(9 to 16 round or 6 to 13

 

square)

Shaft Adapter Type

Self-centering clamping

Materials

Plenum rated plastic housing

Ingress Protection Rating

IP54

Operating Humidity Range (% RH)

5 to 95% RH, non-condensing

Ambient Temperature Range

-40 F to 149F (-40 C to 65 C)

 

-22 F to 150 F (-30 C to 65 C)

 

Two-position models only

Temperature Ratings (Shipping)

-40 F to 150F (-40 C to 65 C)

Storage Temperature Range

-40 F to 150F (-40 C to 65 C)

Weight

3.5 lb (1.6 kg)

Includes

Mounting bracket, self-

 

centering shaft adapter

APPROVALS

 

CE

2006/95/EC

 

(Low Voltage Directive )

 

EMC 2004/108/EC

C-Tick

N314

International Electrotechnical Commission IEC 60730-1 and Part 2—14

Underwriters Laboratories, Inc

UL 873

 

UL1097 for Double Insulation

DIMENSIONS DIAGRAM

 

3-55/64 (98)

3-5/32 (80)

 

1-9/16

1-15/16

47/64

2-27/64 (61)

(40)

(49)

(19)

 

 

 

 

1-1/8

 

 

(29)

 

 

1-1/16

 

 

 

(27)

 

 

 

4-9/16

 

 

 

(116)

6-61/64

 

 

 

(177)

 

 

5-27/32

 

 

(148)

 

2-1/64

M27712A

(55)

s

submittal Sheet