Globe Valve Linkage

Q5022

 

The Q5022A,B Globe Valve Linkages

 

connect one or two Honeywell direct

 

coupled rotary actuators (DCA) to a

 

globe valve for control of chilled water,

 

hot water, or steam. The Q5022A,B

 

Linkages are compatible with 2 and

 

3-way globe valves up to 6 in. (DN150)

 

pipe size.

 

Q5022A is used to provide enhanced

 

close-off ratings with Honeywell globe

 

valves up to 3 in. with 1-3/8 in. diameter

 

bonnet and 3/4 in. stem stroke.

 

Q5022B is used with Honeywell globe

 

valves 4 to 6 in. with 1-7/8 in. diameter

 

bonnet and 1-1/2 in. stem stroke.

 

 

SPECIFICATIONS

 

Linkage Type

Valve

Mounting

Linkage mounts directly to the

 

valve bonnet; motor mounts on

 

linkage

Used with Actuator

Direct Coupled Actuator

Stem Force Rating

1117 lbf max. (4969 N max.)

 

 

FEATURES

For use with 2-way and 3-way globe valves in modulating or two-position service.

For use with 175 lb.-in. (S20) spring return or 175 and 300 lb.-in. (N20, N34) non-spring return DCAs.

Accepts single or dual matching actuators for higher close- off pressures.

Fail-safe operation with spring return DCAs, field selectable normally open or normally closed for direct or reverse- acting valves.

Linkage threads onto valve stem.

Oilite™ self-lubricated actuator shaft bearing.

Anodized extruded aluminum housing.

Maintenance-free construction.

Precision roller-bearing rack construction to prevent premature valve packing wear and leakage.

Flexible actuator mounting orientation.

DIMENSIONS DIAGRAM

 

 

 

STEM STROKE

 

3-1/2

1-1/8

5022A 3/4 (19)

4-7/8

(89)

(28)

5022B 1-1/2 (38)

(124)

 

 

2-1/2

 

 

 

(64)

 

 

 

 

8

 

 

 

(203)

 

 

STROKE “Y”

MAX 6-1/4 (159)

 

 

 

 

3/4 (19)

MIN 2-15/16 (75)

 

 

 

2-1/2

 

M27644

 

(63)

 

 