Honeywell MS4103 manual ML6174 ML7174

Models: MS4103

1 268
Download 268 pages 21 Kb
Page 89
Image 89

Non-Spring Return Direct Coupled Actuator

ML6174; ML7174

Used to control dampers in applications such as variable air volume (VAV) terminal units and for mounting on ball valves; suitable for use with SPDT or floating thermostats or building automation controls.

SPECIFICATIONS

 

Actuator Type

Damper

FEATURES

Control for air damper applications with up to 20 sq.ft. assuming 3.5 lb-in. per sq.ft. of damper area, velocity independent.

Magnetic coupling eliminates the need for mechanical stops or limit switch adjustments by limiting stall torque to 130 lb-in. maximum.

Mount directly on 3/8 to 1/2 in. round and square damper shafts. All models include manual declutch lever for ease of mounting, and bag assembly with two minimum position setscrews. 90 second timing models are suitable for use with pressure independent VAV systems.

Selectable 45, 60, and 90 degree stroke in either clockwise or counterclockwise direction.

DIMENSIONS DIAGRAMS

Rotational Stroke

90 degrees

Fail Safe Mode

Non-Spring Return

Rated Torque

70 lb-in. (8 Nm)

External Auxiliary Switches Available ..

Yes, 201052B

Electrical Connections

Screw terminals

Environmental Rating

NEMA1

Feedback

With accessory

Frequency

50 Hz, 60 Hz

Manual operation

Declutch mechanism

Mounting

Direct Coupled

Maximum Noise Rating,

 

Driving (dBA @ 1m)

45

Timing, Nominal Driving at 60 Hz

90 sec., 180 sec. or 420 sec.

Power Consumption, Driving

2.4 VA or 5.4 VA

Rotation to Open

By wiring

Rotational Stroke Adjustment

Mechanically limited at 45 or

 

60 degrees in cw or ccw

 

directions

Compatible Damper Shafts

3/8 to 1/2 in. square or round

 

(10 to 13 square/round)

Shaft Adapter Type

Aluminum Hub, two set screws

Supply Voltage

24 Vac ±20%

Materials

Steel plate and Plenum rated

 

plastic

Operating Humidity Range (% RH)

5 to 95% RH, non-condensing

Ambient Temperature Range

20 F to 125 F (-18 C to 50 C)

Storage Temperature Range

20 F to 130 F (-18 C to 54 C)

Weight

1.5 lb (0.68 kg)

Includes

4074ENY Bag Assembly

APPROVALS

 

Underwriters Laboratories, Inc

UL873, Plenum Rated

Canadian Underwriters

 

Laboratories, Inc

cUL C22.2 No. 24-93

 

 

2-7/8

(73)

 

 

 

1-11/16

 

 

 

(42)

 

1 (25)

OPTIONAL

1/8

 

 

(3)

 

 

AUXILIARY

 

 

 

 

 

SWITCH

 

CW

4-7/8

 

 

(123)

 

 

 

 

 

COM

4-1/4

 

 

 

 

 

CCW

(108)

 

 

 

 

 

 

11/16

 

 

 

(18)

 

7/8

 

 

 

(22)

3-3/8 (86)

 

1-5/16

 

 

(33)

 

 

 

 

 

 

2-1/2 (64)

 

 

 

M18016

 

 

 

 

1

 

 

 

(25)

 

 

 

5-9/16

 

 

 

(141)

 

 

24 Vac

4-7/8

 

 

(123)

 

 

T1

4-1/4

 

 

T2

(108)

 

 

-

 

 

 

+

 

 

 

+

 

 

 

2-10 Vdc

 

 

 

4-20 mA

 

 

15/32 (12)

 

11/16

 

 

(18)

 

1/8

 

 

 

 

 

(3)

5/16 (8)

 

 

 

 

 

 

1-11/16

 

 

 

(43)

 

 

3-3/8 (86)

 

 

1-13/16 (46)

 

3-5/8 (92)

3 IN. (76 MM)

 

 

 

MINIMUM SPACING

 

 

 

REQUIRED

 

 

 

FOR REMOVING

 

 

 

CONDUIT COVER

 

 

 

7/8 (22)

3-3/4 (95)

2-7/8 (73) 1-11/16

(42)

OPTIONAL

 

AUXILIARY

1/8

SWITCH

 

(3)

1/8

(3)

1-5/16

(33)

3 (76)

M22990

1

(25)

1-13/16

(46)

5-7/8

(149)

M18018

s