Damper And Actuator Sizing

Use the following guidelines to determine the actuator quantity and torque requirements for your damper configuration.

Determine Damper Actuator Locations

Use the following configuration to determine the amount of actuator locations your damper will require.

Single Section 48 x 74 D2, D3

60 x 74 D1

Dampers will never ship more than 2 sections wide and one section high.

Configuration

A single section damper will have one actuator location.

A damper that is 48 x 74 96 x 74 will have one actuator location. This is a two section damper jackshafted together.

A damper that is 96 x 74 144 x 74 will have two actuator locations. This is a two section damper jackshafted together and a single section damper.

Exception: 3 section wide 42 SFT damper will have one actuator location.

If damper exceeds 74” height a second row is necessary. Apply same logic above to each row of dampers.

For dampers larger than 144 x 144, please contact the Take-Off Service (takeoff.service@honeywell.com) for a quote and actuator location.

Mounting

Internal Mount: Blade drive lever bracket provided only. Customer is responsible for providing mounting hardware.

External Mount: Actuator shaft will be provided as extension pin kit to be mounted on side or with jackshaft pre-mounted on damper.

Determining Damper Actuator Torque Requirements

Use the following procedure to determine the required torque for your damper.

NOTE: Damper area is measured using the H and W dimensions.

H

W

M20587

Measuring Damper Area

1.Calculate the damper area in square feet by multiplying the H dimension by the W dimension.

2.Multiply the damper area by the lb-in. per square foot value from Table 2 on page 9.

NOTE: The minimum lb-in. per square foot value that can accommodate tight closeoff and no leakage applications is 5, regardless of the value shown in the table.

3.Select the highest actuator torque value than the calculated value.

EXAMPLE:

Low leakage, parallel blade damper: H dimension = 48 in.

W dimension = 96 in.

Static pressure (in. w.c.) = 2 in. w.c. Face Velocity = 1000 fpm

48 in. x 96 in. ÷ 144 = 32 sq. ft.

32 sq. ft. x 7 lb-in./sq. ft. = 244 lb-in. where 7 lb-in./sq. ft = value from Table 2.

In this case you would need an actuator with a minimum nominal torque of 224 lb-in.