Guide Specifications
Cartridge Globe Valves and Dedicated Actuators
23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
23 09 00 Instrumentation and Control for HVAC
23 09 13 Instrumentation and Control Devices for HVAC
23 09 13.33 Control Valves
Cartridge Globe Valves and Dedicated Actuators
Mounting and Wiring
1.Valves shall be brass with female national pipe thread fittings in sizes from ½ up to 1 ¼ inches (DN15 to DN32) and sweat fittings from ½ to ¾ inches
2.Valves shall be compact size capable of fitting inside terminal equipment such as fan coil units or unit ventilators.
3.Valves ½ to ¾ inches
4.Valves 1 to 1 ½ inches
5.Multiple Cv ratings shall be available in valve sizes ½ to 1 inches
6.
7.Valves bodies shall have static pressure ratings of 230 psig (1600 kPa) at 230°F (110 C), minimum.
8.Actuators shall be direct coupled type requiring neither
9.Actuators shall provide
10.Electronic valve actuators shall be capable of operating on 24 Vac, Class II power (Safety
Control
1.The actuator shall provide
2.Pneumatic actuators shall be available for ½ and ¾ inch
3.Globe valves shall have minimum 50:1 rangeability with an equal percentage or linear flow characteristic.
4.Globe valve proportional actuators shall have response range and travel direction selections.
5.Actuators will be available with optional spring return,
Other
1.All valves must be field serviceable without the need to remove the valve from the piping, in order to minimize future service costs.
2.Valves may not be installed with stems below the horizontal plane to prevent actuator damage due to stem seal leakage, or accumulation of particulate in the stem packing.
3.A water filtration and treatment system shall be installed and operated according to the requirements of Division 23 25 13, Water Treatment for
4.Actuated valves shall be capable of closing off against their maximum operating differential pressure. Seat leakage when closed shall be ANSI/ASME Class III, 0.02% maximum.
5.All actuators must be able to operate from 32 to 122°F (0 to 50 C) ambient temperature, as measured at the actuator.
6.Actuators shall be constructed of materials resistant to condensation when used to control chilled water. Actuator damage due to condensation or falling water shall not be cause for warranty replacement.
7.Proportional actuators shall be designed for a minimum of 50,000
8.All valves and actuators shall be manufactured under ISO 9001 International Quality Control Standards.
9.Valves and actuators shall be as manufactured by Honeywell.