Appendix A: Valve Selection and Sizing

Water Valves

Determine the capacity index (Cv) for a valve used in a water application, using the formula:

Q G

CV = -------------

h

Where:

Q= Flow of fluid in gallons per minute required to pass through the valve.

G

=

Specific gravity of the fluid (water = 1).

h= Pressure drop in psi. See Figures 14 and 15 for glycol solution correction values.

NOTE: The calculated Cv will rarely match the Cv of an avail- able valve. For most accurate proportional control, select the valve with the next lower Cv value, and increase the pressure drop across the control valve to achieve the required flow through the coil by reducing the setting of the balancing valve. Otherwise, turn- down ratio will be reduced, proportionally.

For example, if the calculated Cv is 87, and the two closest Cv values are 63 and 100, the best choice for control precision would be the valve with a Cv of 63, and increase pressure drop across the valve by 90%.

If increased pressure drop is not possible, use the valve with Cv of 100, and accept a 13% reduction in valve rangeability.

For two-position control, always chose the largest Cv greater than the coil with acceptable close-off pressure rating.

Determining the Cv of a water valve requires knowing the quantity of water (gpm) through the valve and the pressure drop

(h)across the valve. If the fluid is a glycol solution, use the pressure drop multipliers from either Figure 14 or 15. See the sections on QUANTITY OF WATER and WATER VALVE PRESSURE DROP. Then select the appropriate valve based on

Cv, temperature range, action, body ratings, etc., per VALVE SELECTION guidelines.

 

1.6

 

 

 

 

 

 

 

 

 

 

 

 

FACTOR

 

 

 

 

40%

 

 

 

 

ETHYLENE

 

 

 

 

 

 

50% BY MASS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GLYCOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SOLUTION

 

 

CORRECTION

1.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30%

 

 

 

 

 

 

 

 

DROP

1.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

40

80

120

160

 

 

 

 

 

 

 

TEMPERATURE, F

 

 

M12226

 

 

 

 

 

 

 

 

 

 

 

 

REPRINTED BY PERMISSION FROM ASHRAE HANDBOOK—

1996 HVAC SYSTEMS AND EQUIPMENT

Fig. 14. Pressure Drop Correction for

Ethylene Glycol Solutions

FACTOR

1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30%

 

50% BY MASS

 

PROPYLENE

 

 

 

 

 

 

 

 

 

 

 

 

GLYCOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40%

 

 

SOLUTION

 

 

CORRECTION

1.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DROP

1.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

40

80

120

160

 

 

 

 

 

 

 

 

TEMPERATURE, F

 

 

M12227

 

 

 

 

 

 

 

 

 

 

 

 

 

REPRINTED BY PERMISSION FROM ASHRAE HANDBOOK—

1996 HVAC SYSTEMS AND EQUIPMENT

Fig. 15. Pressure Drop Correction for Propylene Glycol

Solutions.

Quantity of Water

To find the quantity of water (Q) in gallons per minute use one of the following formulas:

1.When Btu/hr is known:

 

 

 

 

Btu hr

 

 

 

 

 

 

Q = ----------------------

 

 

Where:

 

K TDw

 

 

 

 

 

 

 

Btu/hr=

Heat output.

 

 

K

=

Value from Table 3; based on temperature

 

 

 

of water entering the coil. The value is in

 

 

 

pounds per gallon x 60 minutes per hour.

TDw

=

Temperature difference of water entering

 

 

 

and leaving the coil.

 

 

Table 3. Water Flow Formula Table

 

 

 

 

 

 

 

 

 

Water

 

 

 

Water

Temp F

 

 

K

 

Temp F

 

K

 

 

 

 

 

 

 

 

40

 

502

 

 

200

 

484

60

 

500

 

 

225

 

483

80

 

498

 

 

250

 

479

100

 

496

 

 

275

 

478

120

 

495

 

 

300

 

473

150

 

490

 

 

350

 

470

180

 

487

 

 

400

 

465

254

Page 254
Image 254
Honeywell MS4103 manual Pressure Drop Correction for Ethylene Glycol Solutions