Actuator Wiring Diagrams

Direct Coupled Actuators - Spring Return Models

Direct Coupled Actuators - Spring Return Models

Override to full open (Modulating mode setting)

 

 

 

 

 

ACTUATOR

1

24 VAC

 

 

1

V

2

 

2

 

 

 

 

 

0/2 TO 10 VDC

 

 

 

3

OR +

 

 

 

 

 

PROPORTIONING

 

 

4

OR N/A

CONTROLLER

 

 

 

5

FEEDBACK

 

 

 

 

 

 

 

2-10 VDC

+

 

 

 

 

 

 

SPDT

 

10-2 VDC

 

 

 

3

0-10 VDC

FEEDBACK

 

 

 

 

 

 

 

10-0 VDC

 

 

 

 

 

Fltg, fwd

 

 

 

 

 

Fltg, rev

1LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 24 VDC SUPPLY ACCEPTABLE.

3 SET SWITCH TO MODULATING.

M19576A

Override to full closed (Modulating mode setting)

 

 

 

 

ACTUATOR

1

24 VAC

 

1

V

2

2

 

 

 

 

0/2 TO 10 VDC

 

 

3

OR +

 

 

 

 

PROPORTIONING

 

4

OR N/A

CONTROLLER

 

 

5

FEEDBACK

 

 

 

 

 

2-10 VDC

+

 

 

 

 

SPST

 

10-2 VDC

FEEDBACK

 

3

0-10 VDC

 

 

 

10-0 VDC

 

 

 

 

Fltg, fwd

 

 

 

 

Fltg, rev

1LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 24 VDC SUPPLY ACCEPTABLE.

3 SET SWITCH TO MODULATING.

M19577A

Wiring for Proportioning controllers operating multiple

actuators (Modulating mode setting)

1

24 VAC

ACTUATOR

 

2

1

V

 

 

2

1

24 VAC

 

 

 

 

 

3

OR +

0/2 TO 10 VDC

 

4

OR N/A

PROPORTIONING

5

FEEDBACK

CONTROLLER

 

 

HOT

 

 

 

 

 

 

 

2-10 VDC

 

 

 

 

 

 

 

 

 

 

10-2 VDC

 

COM

 

 

 

 

 

3

 

0-10 VDC

 

 

 

 

 

 

 

 

 

 

10-0 VDC

 

 

 

 

 

 

 

 

 

Fltg, fwd

 

 

+

 

 

 

 

 

 

 

Fltg, rev

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACTUATOR

 

1

 

24 VAC

 

 

 

1

 

V

 

 

2

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

OR +

 

 

 

 

 

 

 

 

4

 

OR N/A

 

 

 

 

 

 

 

 

5

FEEDBACK

 

 

 

 

 

 

 

 

 

 

2-10 VDC

1 LINE VOLTAGE POWER SUPPLY.

 

 

 

 

10-2 VDC

PROVIDE DISCONNECT MEANS AND

 

3

 

0-10 VDC

OVERLOAD PROTECTION AS REQUIRED.

 

 

10-0 VDC

2 24 VDC SUPPLY ACCEPTABLE.

 

 

 

 

Fltg, fwd

 

 

 

 

Fltg, rev

3 SET SWITCH TO MODULATING.

 

 

 

 

M22288

 

 

 

Terminal Block Details

 

 

 

 

 

 

 

 

 

ACTUATOR

 

 

 

85°

 

 

3

 

FEEDBACK

 

 

 

 

 

 

 

 

+

N/A

 

 

 

 

 

 

 

V

OR

OR

 

S1

S2

S3

S4

S5

S6

1

2

3

4

5

2

1

 

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2THE INTERNAL AUXILIARY SWITCHES MUST BE CONNECTED TO THE SAME POWER SOURCE; OR THE AUXILIARY SWITCHES SHALL BE CONNECTED TO THE SAME POLE OF THE SAME SUPPLY CIRCUIT, CONNECTED IN A SAME POLARITY MANNER.

3 ENSURE PROPER GROUNDING OF ACTUATOR CASE.

M19571B

 

WIRING DIAGRAMS

157

Page 157
Image 157
Honeywell MS4103 manual Override to full open Modulating mode setting, Override to full closed Modulating mode setting, 157